RY40NT5P-TS transistor output module
Item
Number of output points
Rated load voltage
Maximum load current
Maximum inrush current
Leakage current at OFF
Maximum voltage drop at ON
Response time
OFFON
ONOFF
Surge suppressor
Fuse
External power
Voltage
supply
Current
Withstand voltage
Isolation resistance
Noise immunity
Protection degree
Wiring method for common
Number of occupied I/O points
Protection
Overload
functions
protection
Overheat
protection
External interface
Internal current consumption (5VDC)
Weight
■Circuit configuration
Internal
circuit
3 SPECIFICATIONS
62
3.1 Performance Specifications
Specifications
16 points
12/24VDC (allowable voltage range: 10.2 to 28.8VDC)
0.5A/point, Pilot Duty, 5A/common
Current is to be limited by the overload protection function.
0.1mA or lower
0.2VDC (TYP.) 0.5A, 0.3VDC (MAX.) 0.5A
0.5ms or less
1ms or less (rated load, resistive load)
Zener diode
None
12/24VDC (ripple ratio: within 5%) (allowable voltage range: 10.2 to 28.8VDC)
6mA (at 24VDC)
510VACrms, 1 minute
10M or higher by isolation resistance tester
Simulator noise 500Vp-p, noise width 1s,
noise frequency 25 to 60Hz (noise simulator condition)
IP2X
16 points/common (common terminal: 18)
Sink type
16 points (I/O assignment: Output 16 points)
Limited current when detecting overcurrent: 1.5 to 3.5A/point
Activated to each point. ( Page 51 Output modules)
Activated to each point. ( Page 51 Output modules)
Two-piece spring clamp terminal block
Page 105 40-pin connector type module
140mA (TYP. all points ON)
0.12kg
Load
1
Load
17
9
Constant-voltage
circuit
18
12/24VDC
Appearance