8
FUNCTIONS
8.1

Input Response Time Setting

This function allows changing the input response times of input modules by each input point. The input modules take in
external input for the set input response time.
ON
OFF
External input
ON
OFF
Input module
Input response time
Setting method
Set the input response time from "input response time setting".
[Navigation window]  [Parameter]  [Module Information]  Module model name  [Module Parameter]  [input
response time setting]
■Input response time and pulse width of noise to be eliminated
The input module may take in noise as an input depending on the input response time setting.
When setting the input response time, consider the environment where the module is used and refer to the following table that
shows the pulse width of noise to be eliminated (pulse width that is not taken in as an input).
Input response time setting value
Pulse width of noise to be eliminated (reference value)
1ms
5ms
0.3ms
1.5ms
10ms
20ms
4ms
8ms
8 FUNCTIONS
8.1 Input Response Time Setting
8
70ms
35ms