S-Bus Sensor Wiring; Interface Overview; User Interface; Keypad - Carrier WeatherMaker 50TC07 Series Installation Instructions Manual

Single package rooftop cooling only with puron (r-410a) refrigerant
Hide thumbs Also See for WeatherMaker 50TC07 Series:
Table of Contents

Advertisement

Table 4 — Economizer Module - Right Hand Terminal
LABEL
TYPE
Top Right Terminal Blocks
AUX2 I
24 vac IN
The first terminal is not used.
Shut Down (SD) or HEAT (W)
Conventional only
OCC
24 vac IN
and
Heat Pump Changeover (O-B) in Heat
Pump mode.
E-GND
E-GND
Occupied/Unoccupied Input
EXH1
24 vac OUT Exhaust Fan 1 Output
Programmable:
Exhaust fan 2 output
or
AUX1 O
24 vac OUT
ERV
or
System alarm output
Bottom Right Terminal Blocks
Y2 in - Cooling Stage 2 Input from space
Y2-I
24 vac IN
thermostat
Y2 out - Cooling Stage 2 Output to stage
Y2-O
24 vac OUT
2 mechanical cooling
Y1 in - Cooling Stage 2 Input from space
Y1-I
24 vac IN
thermostat
Y1 out - Cooling Stage 2 Output to stage
Y1-O
24 vac OUT
2 mechanical cooling
C
COM
24 vac Common
R
24 vac
24 vac Power (hot)

S-BUS SENSOR WIRING

The labels on the sensors and controller are color coded for
ease of installation. Orange labeled sensors can only be wired
to orange terminals on the controller. Brown labeled sensors
can only be wired to S-bus (brown) terminals. Use Fig. 93 and
Table 5 to locate the wiring terminals for each S-Bus sensor.
Use Fig. 93 and Table 5 to locate the wiring terminals for each
enthalpy control sensor.
S-BUS
TERMINALS
(1 AND 2)
Fig. 93 — S-Bus Sensor DIP Switches
Blocks
DESCRIPTION
DIP
SWITCH
LABEL
DIP
SWITCHES
(3)
S-BUS
2 PIN SIDE
CONNECTOR
Table 5 — HH57AC081 Sensor Wiring Terminations
TERMINAL
NUMBER
LABEL
1
S-BUS
2
S-BUS
Use Fig. 93 and Table 6 to set the DIP switches for the desired
use of the sensor.
Table 6 — HH57AC081 Sensor DIP Switch
DIP SWITCH POSITIONS FOR SWITCHES 1, 2, AND 3
USE
1
DA
OFF
RA
ON
OA
OFF
NOTE: When a S-Bus sensor is connected to an existing network,
it will take 60 minutes for the network to recognize and auto-con-
figure itself to use the new sensor.
During the 60 minute setup period, no alarms for sensor fail-
ures (except SAT) will be issued and no economizing function
will be available.
CO
SENSOR WIRING
2
When using a CO
sensor, the black and brown common wires
2
are internally connected and only one is connected to "IAQ
COM" on the W7220. Use the power from the W7220 to pow-
er the CO
sensor OR make sure the ground for the power sup-
2
plies are common. See Fig. 94 for CO
CO
SENSOR
2
24V
ANALOG
OUT
1
POWER SUPPLY. PROVIDE DISCONNECT
MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
Fig. 94 — CO

INTERFACE OVERVIEW

This section describes how to use the Economizer's user inter-
face for:
Keypad and menu navigation
Settings and parameter changes
Menu structure and selection

USER INTERFACE

The user interface consists of a 2-line LCD display and a 4-but-
ton keypad on the front of the economizer controller.

KEYPAD

The four navigation buttons (see Fig. 95) are used to scroll
through the menus and menu items, select menu items, and to
change parameter and configuration settings.
57
TYPE
DESCRIPTION
S-BUS
Communications
S-BUS
(Enthalpy Control
Sensor Bus)
S-BUS
Communications
S-BUS
(Enthalpy Control
Sensor Bus)
2
ON
OFF
OFF
OFF
OFF
OFF
sensor wiring.
2
RED
L1
(HOT)
BLACK
L2
1
YELLOW
+
BROWN
ORANGE
GREEN
Sensor Wiring
2
3