Step 9 - Install External Condensate Trap And Line - Carrier WeatherMaker 50TC07 Series Installation Instructions Manual

Single package rooftop cooling only with puron (r-410a) refrigerant
Hide thumbs Also See for WeatherMaker 50TC07 Series:
Table of Contents

Advertisement

9.
Replace the filter access panel.
INDOOR
COIL
ACCESS
PANEL
Fig. 29 — Indoor Coil Access Panel Relocation
(Size 16)
LEFT
HOOD
SIDE
Fig. 30 — Economizer Hood Construction (Size 16)
DIVIDER
CLEANABLE
ALUMINUM
FILTER
BAROMETRIC
RELIEF
Fig. 31 — Economizer Filter Installation (Size 16)
SIDE
PANEL
RAIN DEFLECTORS
TOP
PANEL
CAULK
HERE
INDOOR
COIL
ACCESS
PANEL
TOP
PANEL
INDOOR COIL
ACCESS PANEL
SCREW
HOOD DIVIDER
OUTSIDE
AIR
HOOD
FILTER
Step 9 — Install External Condensate Trap and
Line
The unit has one
of the condensate pan and an alternate connection on the bot-
tom. See Fig. 32. Unit airflow configuration does not deter-
mine which drain connection to use. Either drain connection
can be used with vertical or horizontal applications.
When using the 50TC*16 standard side drain connection, en-
sure the red plug in the alternate bottom connection is tight. Do
this before setting the unit in place. The red drain pan can be
tightened with a
To use the alternate bottom drain connection, remove the red
drain plug from the bottom connection (use a
socket drive extension) and install it in the side drain
connection.
CONDENSATE PAN (SIDE VIEW)
STANDARD
SIDE DRAIN
Fig. 32 — Condensate Drain Pan (Side View)
The piping for the condensate drain and external trap can be
completed after the unit is in place. See Fig. 33.
MINIMUM PITCH
1˝ (25 mm) PER
10´ (3 m) OF LINE
TO ROOF
DRAIN
NOTE: Trap should be deep enough to offset maximum unit static
difference. A 4-in. (102 mm) trap is recommended.
Fig. 33 — Condensate Drain Piping Details
All units must have an external trap for condensate drainage.
Install a trap at least 4-in. (102 mm) deep and protect against
freeze-up. If drain line is installed downstream from the exter-
nal trap, pitch the line away from the unit at 1-in. per 10 ft
(25 mm in 3 m) of run. Do not use a pipe size smaller than the
unit connection (
See Fig. 34-45 for wiring diagrams.
FILTER
CLIP
25
3
/
-in. condensate drain connection on the end
4
1
/
in. square socket drive extension.
2
DRAIN
PLUG
(FACTORY-INSTALLED)
BASE RAIL
3˝ (76 mm)
MIN
OPEN
VENT
DRAIN PLUG
3
/
-in.).
4
1
/
-in. square
2
ALTERNATE
BOTTOM DRAIN
SEE NOTE
ROOF
CURB