Swegon LUNA c RE Manual page 26

Room temperature controller and configuration device
Table of Contents

Advertisement

ACP0
A = All reset (all values are reset to factory
default) Note! This can only be done with a
special code, contact Swegon.
C = Resets all, except the clock and certain
important system parameters.
P = "Regular" reboot. Values read from the
controller is copied to the confi guration
unit's fi rm memory.
0 = Not used. Has to be 0!
Press the SET-button to jump between the diffe-
rent reset functions, and confi rm your selection
by pressing the UP button.
"Addri" and "DATA"
Reading the values in the configuration device's
RAM.
To be able to perform some types of fault
localisation it may be necessary to read some of
the values in the RAM. The address is entered at
the view "Addri", and the value can then be read
at the view "DATA".
When you are at the menu view ("Addri"), you
can press the SET button twice, and with the UP
button change to menu view ("Addre"). This
indicates that the will read the controller's RAM
directly, instead of the confi guration device's
RAM. Press the SET button again to confi rm the
selection.
"INIT" is only used to program some customer specifi c
initiation values, contact Swegon.
"CODEG" and "CODES" Special code for protected
system functions.
Some functions are protected to prevent that any
harware related settings are done incorrectly. But
sometimes it may be necessary.
The view "CODEG" generates a temporary code.
Write this code down, and then contact
Swegon to get the access code. The access code
is then entered at the display view "CODES".
2009-05-22
www.swegon.com
26