Menu "Outputs - Swegon LUNA c RE Manual

Room temperature controller and configuration device
Table of Contents

Advertisement

3.16 Menu "Outputs"

This menu allows you to select different functions for
all the controller's outputs. There is two 24V ouputs
and two 0-10V ouputs. These are designated as "d1",
"d2", "A1" and "A2".
d1 and d2 are digital on/off outputs.
A1 and A2 are analog outputs.
The terminal on the circuit board has a limited amount
of in and outputs. As default there are two 24V outputs
and two inputs (external sensor and condensation sen-
sor) available. To be able to change this, the changes
have to be made in the output menu fi rst, and then
change the jumper settings on the controller as de-
scribed on page 7.
To select an output, select the display view "OUT.
no".
Press the SET-button, and "d1" starts to blink. Use the
UP and DOWN buttons to select an output. Press the
select button again to confi rm the selection.
All the views, "TYPE" to "MOT" are now valid for the
selected output.
"TYPE" Output type
Selectable output types:
- On /off
- Time proportional on/off (PWM) "PULS"
- 0-10V
- No output
Depending on the selected output, only the
applicable signal types is shown for each output.
Output "d1" has also a signal type "3P", but this
has no function in this version of the controller.
"HC:" Heating or cooling output
Select if the output should be a heating or
cooling output. It is possible to control both
heating and cooling, for mixing dampers etc. The
output can also be affected directly by the room
temperature by setting desired limit values on the
"LIML" and "LIMH" display views.
- Cooling output
"COOL"
- Heating output
"HEAT"
- Heating/cooling
"HC"
- Absolute temperature "dIFF"
"OnOF"
"0-10"
"-"
2009-05-22
Menu 4
Outputs
MENU
4
OUTP
Output number
d1
OPno
Output type
PULS
TYPE
Heating/Cooling
COOL
HC:
Override
0
FORC.
Control range,
lower
0
LIML%
Control range,
higher
100
LIMH%
Voltage limit,
lower
-
LIML V
Voltage limit,
higher
-
LIMH V
Period time
20.0
PTIME
Invert output
0
INV.
Valve excercise
1
MOT.
Menu "Outputs"
www.swegon.com