3.18 Menu "occupancy"

The controller has functions to override the operation
mode with a occupancy detector. A simple passive IR
detection unit can be used, if it has a potential free
relay or equivalent.
"ACTIV" Occupancy function activation
To activate this function, this value is set to 1.
If the override isn't affected by the timer or an
external override function, the operation mode
will change from "DAY" to "NIGHT".
When occypancy is detected, the operation mode
will change to "DAY".
"NO" Normally open contact
To suit the most common IR detection units,
a contact function can be selected for the IR
detection unit's relay.
NO = 0 relay open at detection
NO = 1 relay closed at detection
"TIME 0" Off delay
An off delay time can be set for the occupancy
sensor input. The value can be set from 0 to 990
minutes with steps of 1 up to 100 minutes. The
steps will after that change to 10 minute steps.
As soon as the occupancy sensor contact stops
indicating, the off delay starts it's countdown.
After the delay is timed out the controller will
change it's operation mode back to "NIGHT".
"TIME1" On delay
The on delay time is set as a time delay before
the controller activates the operation mode
"DAY" when occupancy is detected. The value
can be set from 0 to 99 minutes.
When occupancy is detected, the controller
receives an impulse from the detector, and the on
delay starts to count. If no new impulses are
received, the current operation mode will not
change. If the controller recives one or more
impulses, the "DAY" operation mode will be
activated when the controller has completed it's
countdown of the set up on delay time.
This function is useful if you wan't to prevent the
controller from changing it's operation mode from
"NIGHT" when you just pass the room quickly.

3.19 Menu "Calibration"

The calibration menu allows you to calibrate the
controller's built-in (R1) or external temperature
sensor (R2).
2009-05-22
Menu 6
Occupancy
MENU
6
OCC
Occupancy
function
0
ACTIV
Occypancy contact
function
0
NO
Off delay
60
TIME 0
On delay
0
TIME 1
Menu "Occupancy"
Menu 7
Calibration
MENU
7
CAL
Built-in sensor
0.0
R1
External sensor
0.0
R2
Menu "Calibration"