3.20 Menu "Button functions"

At this menu you can set the controllers main view
functions, enter an access code and set max/min limits
to the "DAY" operation mode.
"CODE:" Access code
An access code can be set to prevent unauthori -
zed access to the controller. A system code can be
set to prevent access to the settings menu.
By default the code is set to "0000", this code
also inactivates the code function.
"MAX.T" Maximum timer time
It's possible to set a maximum limit for the timer's
time function, in hours between 0 to 255.
If the value 0 is set, the function is inactive and
can't be activated from the main menu.
Default value is 255.
"MINSP" and "MX SP" Set-point scale limit
"MIN B" is the lowest set-point value for the set-
point scale, default value is 16°
"MX SP" is the highest set-point value for the set-
point scale, default value is 28°
"LOCK" The "lock" function for the clock etc.
A lock function can be activated to different
values at the main menu. If the value 1 is set, all
the menu view's is still visible, but the following
values can not be changed:
- Day, time, date, year
- "NIGHT" operation mode set-point value
- "SAVE" operation mode set-point value
"ENG." Language setting
Select language:
0 = Swedish
1 = English
The value is also saved to the controller next time
you connect. If the controller is reset, the
language settings resets to the controllers default
value (1).
2009-05-22
Menu 8
Knappfunktioner
MENU
8
BUT.F
Code
0000
CODE:
Main display view
1
GRND
Measure value
view
1
MEAS.
Select function
0
SEL.F
Select time
5
SEL.T
Maximum timer
time
255
MAX.T
Minimum set-point
value
16.0
°C
MINSP
Maximum set-
point value
28.0
°C
MX SP
Activate code
0
LOCK
Language setting
1
ENG.
Menu "Button functions"
www.swegon.com
24