3.14 Menu "Log"

The controller has a built-in log function, where it can
store the room temperature with the set up inteval.
The interval is set to 1 time/hour as default.
The controller can store up to 75 log values.
The interval is set at the view "L.TIME", and can be
set from 0-255 minutes. The value 0 deactivates the
log function.
To read the logged values, set the desired log number
(from 1-75) at the "MV.no" view where point 1 is the
latest logged value. The logged value can then be read
at the "MEAS." view.
3.15 Menu "Control parametres"
All the controllers control parameters can be set under this menu.
The parametres are:
"DB.D"
Dead band, day mode
"DB.N"
Dead band, night mode
"DB.S"
Dead band, save mode
"P.H"
P-range, heating
"P.C"
P-range, cooling
"I.H"
I-time, heating
"I.C"
I-time, cooling
0.5 - 20.0 K
0.5 - 20.0 K
0.5 - 20.0 K
0.5 - 99.5 K
0.5 - 99.5 K
0.5 - 99.5 minutes
0.5 - 99.5 minutes
2009-05-22
Menu 2
Log
MENU
2
LOG
Log time
60
L.TIME
Measure value
number
1
MV.NO
Measured value
0.0
°
MEAS.
Menu "Log"
Menu 3
Control parametres
MENU
3
REGUL
Dead band, day
1.0
DB.D
Dead band, night
4.0
DB.N
Dead band, save
8.0
DB.S
P-range, heating
1.5
P.H
P-range, cooling
1
P.C
I-time, heating
20.0
I.H
I-time, cooling
20.0
I.C
Menu "Control parametres"
www.swegon.com
19