3.21 Menu "Test"

This menu allows you to monitor the controller's in
and outputs, make temperature simulations, reset the
software etc.
"IN:" Input status
Reading the input status IN1 and IN2.
0 = inactive, 1= active
If IN1 is used for an external sensor, the number 1
is shown if the sensor is connected.
"OUT:" Output status
At this view you can see the status of the control-
lers two 24V outputs. The number to the right
shows the status of output "d2", and the number
at the center shows the status for output "d1"
The number to the left can be set to 1 if you wish
to force any of the outputs to be active by
pressing the SET button and then the UP button
(the control functions are automatically turned
off). Then press the SET button again to jump to
the next number (output). The value can be set
to 1 or 0 to force the action of the outputs.
If any of the outputs has been activated by force,
the symbol AUTO will blink. The function will
deactivate automatically after 2 hours, or at
voltage failure.
"TST.R" Space temperature override
To make simulations and tests of the control
functions in the controller, the room temperature
sensors reading can be deactivated. Instead, you
can enter a (simulated temperature) value
manually at the main menu view by fi rst
activating the override at the "TST.R" view, and
the return to the main view and press the SET
button, and enter a (simulated room temperature)
value. The function will deactivate automatically
after 2 hours, or at voltage failure.
"RESET" Reset
The controllers reset functions can reset the con-
trollers software or all the controller's values to
factory default. The reset functions are:
(continues on the next page)
2009-05-22
Menu 9
Test menu
MENU
9
TEST
Inputs
00
IN:
Outputs
010
OUT:
Space temperature
override
0
TST.R
Reset functions
ACP0
RESET
Address internal
Address external
288
Addre
Addri
Address data inter-
nal/external
255
DATA:
Customer initiation
0
INIT.
Generated code
3957
CODEG
System code
0000
CODESS
Inverted LED
0
LIGHT
Menu "Test"