Checking For Errors And Troubleshooting On The Sysmac Studio; Checking For Errors From The Sysmac Studio - Omron NX Series User Manual

Machine automation controller system units
Hide thumbs Also See for NX Series:
Table of Contents

Advertisement

5-3
Checking for Errors and Trouble-
shooting on the Sysmac Studio
Error management on the NX Series is based on the methods used for the NJ-series Controllers.
This allows you to use the Sysmac Studio to check the meanings of errors and troubleshooting proce-
dures.
5-3-1

Checking for Errors from the Sysmac Studio

When an error occurs, you can place the Sysmac Studio online to the Controller or the Communications
Coupler Unit to check current Controller errors and the log of past Controller errors.
The methods that are used to check errors depend on the Controller you use.
Controller
used
NJ-series
Controller
Other control-
lers
*1. On NX Units that manage their own errors, current errors cannot be checked after a fatal error occurs in that
NX Unit. On NX Units that record their own event logs, the error log cannot be checked after a fatal error occurs
in that NX Unit.
Refer to the NJ-series Troubleshooting Manual (Cat. No. W503) for information on NJ-series error man-
agement methods.
Refer to the NJ-Series Sysmac Studio Version 1 Operation Manual (Cat. No. W504) for details on trou-
bleshooting with the Sysmac Studio.
If you cannot check the error on the Sysmac Studio, check the error by following the flow outlined in 5-6
Troubleshooting Flowchart on page 5-14.
Additional Information
Checking Errors in an EtherCAT Slave Terminal with an NS-series PT
You can use an NS-series PT to view current errors on the EtherCAT Coupler Unit errors and
some of the NX Units as well as information on the NX Units in which current errors occurred.
You cannot use it to check event logs and details on current errors in the NX Units.
NX-series System Unit User's Manual (W523)
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Sysmac Studio
connection
NJ-series CPU Unit
You can check the errors that are
managed by the Controller. This
includes errors for the connected
EtherCAT Slave Terminals.
EtherCAT Coupler
You can check the errors that are
Unit
managed by the EtherCAT Coupler
Unit. You can check errors in the
EtherCAT Coupler Unit to which the
Sysmac Studio is connected, and
errors in the NX Units that are con-
nected after the EtherCAT Coupler
Unit.
EtherCAT Coupler
Same as above.
Unit
Scope of check
You cannot check errors if there is
a fatal error in the CPU Unit.
• You can check errors in the Slave
• You cannot check errors if there
• Some errors in the NX Units can-
Same as above.
5 Troubleshooting
Remarks
Terminals even if there is a fatal
error in the CPU Unit.
is a fatal error in the EtherCAT
Coupler Unit.
not be checked if a fatal error
*1
occurs in that NX Unit.
5
5 - 5

Advertisement

Table of Contents
loading