Electrical Installation - Siemens MICROMASTER Eco Operating Instructions Manual

Frequency inverter for fans and pumps
Hide thumbs Also See for MICROMASTER Eco:
Table of Contents

Advertisement

ELECTRICAL INSTALLATION .........................................

Control
Terminals
Input
Supply
Terminals
Motor
Terminals
MICROMASTER Eco - Mains supply, motor
and control connections
L1 L2 L3
MIDIMASTER Eco - Power and motor
connections.
Make sure that the Eco is securely mounted.
For 110kW to 315kW units the mains supply
terminals are at the top, and the motor
connection terminals are at the bottom.
6
DIP
Switch's
FS7 units
L1
L2
L3
U
V
W
PE
DC- DC+
PE
FS6 units
L1
L2
L3
U
V
FS4/5 units
PE PE
DC- DC+ U V W
Power and Motor terminals
CONNECTING TO MAINS
Terminals L/L1, N/L2 & L3
Ensure that the nameplate voltage of the Eco
(and the motor) corresponds to the mains
supply voltage to be used.
Check that the supply circuit protection is
correctly rated for the Eco nameplate input
current.
Ensure that all power cables are adequately
rated for the expected duty.
CONNECTING TO MOTOR
Terminals U, V, & W
Only use the Eco with fan or pump motors
(variable torque).
DIRECTION OF ROTATION
The direction of rotation of the motor can be
reversed by changing over two of the output
connections on the Eco.
W
NOTE
The power cable screen and control wiring
screen must be connected to the inverter gland
plate.
PE
U
V
W
x
x
x
x
M
PE
U
V
W
x
x
x
x
M

Advertisement

Table of Contents
loading

This manual is also suitable for:

Midimaster eco

Table of Contents