M-system 47LPT Operating Manual

M-system 47LPT Operating Manual

Vt input digital panel meter

Advertisement

Quick Links

OPERATING MANUAL
VT INPUT DIGITAL PANEL METER
(4 1/2 digit, LED display type, true RMS sensing)
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System's Sales Office or representatives.
■ PACKAGE INCLUDES:
Digital panel meter ...................................................... (1)
Engineering unit sticker label sheet ........................... (1)
■ MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■ OPERATING MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection,
basic maintenance procedures and detailed operations.
POINTS OF CAUTION
■ CONFORMITY WITH EC DIRECTIVES
• This equipment is suitable for use in a Pollution Degree 2
environment and in Measurement Category III, Installa-
tion Category II, with the maximum operating voltage of
300V.
Reinforced insulation is maintained between signal input,
output and power input. Prior to installation, check that
the insulation class of this unit satisfies the system re-
quirements.
• Altitude up to 2000 meters
• The equipment must be installed such that appropriate
clearance and creepage distances are maintained to con-
form to CE requirements. Failure to observe these re-
quirements may invalidate the CE conformance.
• In order to enable the operator to turn off the power input
immediately, install a switch or a circuit breaker accord-
ing to the relevant requirements in IEC 60947-1 and IEC
60947-3 and properly indicate it.
■ POWER INPUT RATING & OPERATIONAL RANGE
Locate the power input rating marked on the product and
confirm its operational range as indicated below:
100 – 240V AC rating: 85 – 264V, 50/60 Hz, approx. 6.5VA
24V DC rating: 24V ±10%, approx. 3W
110V DC rating: 85 – 150V, approx. 3W
■ GENERAL PRECAUTIONS
• Before you remove the unit or mount it, turn off the power
supply and input signal for safety.
• Be sure to put the terminal cover on while the power is
supplied.
MODEL
■ ENVIRONMENT
• Indoor use
• When heavy dust or metal particles are present in the air,
install the unit inside proper housing with sufficient ven-
tilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
• Be sure that the ventilation slits are not covered with ca-
bles, etc.
■ REQUIREMENTS TO ENSURE IP66
• Observe the designated panel cutout size (W92 × H45
mm).
• The watertight packing included in the product package
must be placed behind the front cover.
• Both mounting brackets must be fastened tightly until
they hit the panel.
• Confirm visually that the packing is not contorted or ex-
cessively run off the edge after installation.
■ WIRING
• Make sure for safety that only qualified personnel per-
form the wiring.
• Do not install cables (power supply, input and output)
close to noise sources (high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■ AND ....
The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for sat-
isfying complete performance described in the data sheet.
47LPT
47LPT
EM-9506-B Rev.6
P. 1 / 16

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 47LPT and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for M-system 47LPT

  • Page 1 ■ ENVIRONMENT BEFORE USE ..• Indoor use • When heavy dust or metal particles are present in the air, Thank you for choosing M-System. Before use, please check install the unit inside proper housing with sufficient ven- contents of the package you received as outlined below. tilation. If you have any problems or questions with the product, • Do not install the unit where it is subjected to continuous...
  • Page 2: Component Identification

    47LPT COMPONENT IDENTIFICATION n TOP VIEW Strap Specifications Watertight Sealing n FRONT VIEW n SIDE VIEW Mounting Bracket Terminal Cover (1) Main Display (2) Alarm Indicators Spn D/P Min Max (3) Function Indicators Max/Min Alarm/ Scale/ Shift (8) Up Button...
  • Page 3: Installation

    47LPT INSTALLATION ■ HOW TO MOUNT THE UNIT ON A PANEL ■ PANEL CUTOUT unit: mm The watertight packing must be in place to hold the meter. + 0.8 Do not remove it. – 0 1) Insert the unit into the panel cutout.
  • Page 4 47LPT ■ CONNECTION DIAGRAM ■ ALARM SUFFIX CODE 0: No alarm output SOURCE FUSE DC OUTPUT – LOAD U(+) POWER V(–) ■ ALARM SUFFIX CODE 1: N.O. contact, 4 points ■ ALARM SUFFIX CODE 2: SPDT contact, 2 points SOURCE...
  • Page 5: Setting Procedure

    47LPT SETTING PROCEDURE INITIAL SETTING FLOWCHART POWER ON Hold down Scale/ button for 3 seconds or more to move on to Scaling Setting Mode. Choose an input type and display scale values. Hold down Alarm/ button for 3 seconds or more to move on to Alarm Setting Mode.
  • Page 6 47LPT ■ OPERATIONS IN MEASURING MODE • Switching the main display to MAX or MIN values Press Max/Min button to switch the main display to MAX or MIN values. ‘Max’ or ‘Min’ indicator turns on during the MAX/MIN display mode. Press Max/Min button again for 1 second or more, or turn the power supply off and on to cancel the MAX/MIN display mode. Max/Min Max/Min button button Measuring Max. Value Min. Value Mode Display Display Max/Min button • Forced Zero Display Forced Zero Canceled...
  • Page 7 47LPT ■ OPERATIONS IN SETTING MODES • Main display The main display shows the current settings while the panel meter is in the setting mode. • Shifting through setting parameters In any setting mode, pressing Alarm/ button shifts one parameter to the next. Pressing Scale/ button shifts one to the previous. • Changing parameters Pressing Shift button while one of the parameter settings is indicated on the display shifts the panel meter into the setting standby mode.
  • Page 8 47LPT DEFAULT PARAMETER INDICATORS DISPLAY FUNCTION VALUE Measuring range 0 to 150V Input type Measuring range 0 to 300V Input value for Zero point: Input scaling value A Set to a specific value by using the buttons, or by Teach Calibration...
  • Page 9 47LPT • Normal Scaling • Inverted Scaling The display value increases when the input signal increases. The display value decreases when the input signal increases. Display Display Full Scale Zero Display Scaling Display Scaling Zero Full Scale Input Input Input Scaling Input Scaling •...
  • Page 10 47LPT ■ ALARM SETTING MODE Measuring Mode Hold down Alarm/ button Hold down Alarm/ or Scale/ button for ≥3 seconds for ≥1 second Alarm Setting Mode Setting Parameters Scale/ Set value Shift 2 / 4* Alarm Point Alarm/ Scale/ Alarm/...
  • Page 11 47LPT Alarm/ Scale/ Alarm/ Scale/ Shift -19999...19999 H Setpoint Alarm/ Scale/ Alarm/ Scale/ Shift LMHI / LMLO H Trip Action Alarm/ Scale/ Alarm/ Scale/ Shift 0000...9999 H Deadband Alarm/ Scale/ Alarm/ Scale/ Shift 00...99 H ON Delay Time Alarm/ Scale/...
  • Page 12 47LPT DEFAULT PARAMETER INDICATORS DISPLAY FUNCTION VALUE Dual alarm: L, H Alarm points Quad alarm: LL, L, H, HH LL setpoint LL: Setpoint value LL: Hi trip LL trip action LL: Lo trip LL: Deadband (hysteresis) value LL deadband (hysteresis)
  • Page 13 47LPT ■ ADVANCED SETTING MODE Measuring Mode Hold down Alarm/ + Scale/ button Hold down Alarm/ or Scale/ button at once for ≥3 seconds for ≥1 second Advanced Setting Mode Setting Parameters Scale/ Set value Shift OFF / 2 / 4 / 8 / 16 / 32 / 64...
  • Page 14 47LPT DEFAULT PARAMETER INDICATORS DISPLAY FUNCTION VALUE No moving averaging Moving average Moving average with 2 samples Moving average with 4 samples Moving average with 8 samples Moving average with 16 samples Moving average with 32 samples Moving average with 64 samples...
  • Page 15 47LPT ■ LOCKOUT SETTING MODE Measuring Mode Hold down Alarm/ + Max/Min button Hold down Alarm/ or Scale/ button at once for a preset time* for ≥1 second Lockout Setting Mode Setting Parameters Set value Shift OFF / ON Alarm Setting Lockout...
  • Page 16: Error Messages

    M-System’s option, the repair, replacement or refund of the purchase price of any M-System product which is defective under the terms of this warranty. To submit a claim under this warranty, the purchaser must return, at its expense, the defective M-System product to the below address together with a copy of its original sales invoice.