Serial Communication Port (Rs-232C) Transmission; Specifications; Byte-Swap Mode Specifications - Toshiba PA912 Instruction Manual

Profibus module for unified nv series controller
Table of Contents

Advertisement

Appendix A Specifications
A.5

Serial Communication Port (RS-232C) Transmission

Specifications

A.6

Byte-swap mode Specifications

order in TC-net I/O loop common area ,both Input and Output area, via
PROFIBUS Slave I/Os by referring the Slave I/O's configuration information.
ordinarily. Expectation is the case of which Slave I/O transfer its data to
PROFIBUS as little-endian order with word-type. Data transferring type is
depend on the Slave I/O's manufacturer's specification, and At that case User
is needed to send byte-swap command by nv-tool (Detail is described at
Chapter. 3 )
90
6F8C1259
Table A-6 Serial specifications
Item
Data transmission
speed
Synchronization
method
Transmission cable
Cable length
Communication method Half duplex
Communication setting
With Byte-swap mode,PA912 automatically rearrange data of the byte address
So, data in TC-net I/O loop common area is converted to little-endian
Table A-7 PROFIBUS I/O's Transfer specifications
PROFIBUS Slave I/O
Transfer Specification
Data
Format type
Byte
Word
○ :Order in the TC-net common area is correct .and No need for
additional setting.
□:Order in the TC-net common area is incorrect.(Byte-swap is
occurs) and User is needs for additional setting by nv-tool.
×: Order in the TC-net common area is incorrect.(Byte-swap is
occurs). and User is needs to set PA912 as byte-swap mode.
Specifications
Max. 9600 bps
Asynchronous
Cross cable with 9-pin-9-pin D-sub connector
Max. 15 m
・Parity bit: none
・Character length: 8 bits
・Stop bit: 1 bit
Order
Big-endian
Little-endian
Byte-swap
mode
Valid
In-valid
×
×

Advertisement