Chapter 3 Setting
offset b15 b14 b13 b12 b11 b10
0
Name
ONL
PF MODE 00: PA912 PROFIBUS transmission in ONLINE status
DVSTS
DVER
NPR
TXER
NDT
ACL
offset b15 b14 b13 b12 b11 b10
1
58
6F8C1259
PF module status (PA_MDL_STS_ ** )
Indicates the PROFIBUS transmission status of the PA912.
ONL
PF MODE
Figure 3-33 PF module status
Table 3-4 PF module status
1: PA912 in PROFIBUS transmission with one or more devices
0: PA912 not in PROFIBUS transmission with other devices
01: PA912 PROFIBUS transmission in STANDBY status
10: PA912 PROFIBUS transmission in NOT OPERATE status
11: PA912 PROFIBUS transmission in DOWN status
00: Transmission module (PROFIBUS-DP transmission I/F module) in OFFLINE status
01: Transmission module (PROFIBUS-DP transmission I/F module) in STOP status
10: Transmission module (PROFIBUS-DP transmission I/F module) in CLEAR status
11: Transmission module (PROFIBUS-DP transmission I/F module) in OPERATE status
1: Transmission module (PROFIBUS-DP transmission I/F module) in error status
0: Transmission module (PROFIBUS-DP transmission I/F module) in normal operation
1: Activation request exists
0: No activation request exists
1: Transmission error exists
0: In normal operation
1: Halted slave exists
0: In normal operation
1: Automatic clear mode is enabled
0: Automatic clear mode is not enabled
Remark
"ACL(Automatic clrear mode)" bit of the Tabele 3-4 PF modeule status is setted as
same status as you setted with HMS confgurator tool.If the ACL is setted as
1( enable),The output data from PA912 to Profibus Slave I/Os via PROFIBUS network will
be cleared(setted as "0" ) in the case some harmful problem is occured on the PROFIBUS
network and PA912 found the disconnected to Profibus Slave I/Os.
Healthy counter (PA_HLTY_CNT_ ** )
Indicates the normal operation status of the PROFIBUS-DP transmission I/F
module connected to the PA912.
It is a 16-bit counter updated in intervals of 100 ms, which indicates that
the PROFIBUS-DP transmission I/F module is in normal operation. The
counter returns to 0000h after FFFFh.
Figure 3-34 Healthy counter
b9
b8
b7
b6
b5
DVSTS
DVER
NPR
Description
b9
b8
b7
b6
b5
Healthy counter
b4
B3
b2
b1
b0
TXER
NDT
ACL
b4
B3
b2
b1
b0