5.8 (Optional) Installing the Power Cable of the Tracking
System
Precautions
The tracking system should be equipped with an overcurrent protective device/component.
The power cable between the device/component and wiring terminal should be no longer than
2.5 m.
Connecting the Power Cable to the Power Port for the Tracking System
Step 1 Remove the sealing nut from the cable gland.
Step 2 Prepare a cable.
Step 3 Route the cable through the cable gland.
Step 4 Connect the power cable of the tracking system.
Step 5 Bind the power cable of the tracking system.
Step 6 Tighten the cable gland.
Issue 10 (2020-03-28)
The tracking system is powered by the three-phase AC power grid with a rated voltage of
800 V.
Keep inflammable materials away from the power cable.
The power cable must be protected with a conduit to prevent short circuits caused by
insulation layer damage.
If there is a power port for the tracking system in the maintenance compartment of the
inverter, connect the power cable of the tracking system to the power port.
If there is no power port, connect the power cable to the AC terminal block.