SUN2000-(90KTL, 95KTL, 100KTL, 105KTL) Series
User Manual
Parameter
Grid connected recovery time
from grid faults (s)
Startup voltage lower threshold
of grid connection (V)
Startup frequency upper
threshold of grid connection (Hz)
Startup frequency lower
threshold of grid connection (Hz)
Grid reconnection voltage upper
limit (V)
Grid reconnection voltage lower
limit (V)
Grid reconnection frequency
upper limit (Hz)
Grid reconnection frequency
lower limit (Hz)
Reactive power compensation
(cosφ-P) trigger voltage (%)
Reactive power compensation
(cosφ-P) exit voltage (%)
----End

7.1.5.2 Setting Protection Parameters

Procedure
Step 1 Choose Settings > Protection parameters to set protection parameters.
Issue 10 (2020-03-28)
Description
Specifies the time after which the inverter begins restarting after the power
grid recovers.
According to the standards of certain countries and regions, after the
inverter is powered on for the first time for grid connection, if the power
grid voltage is lower than Startup voltage lower threshold of grid
connection, the inverter is not allowed to connect to the grid.
According to the standards of certain countries and regions, after the
inverter is powered on for the first time for grid connection, if the power
grid voltage is higher than Startup frequency upper threshold of grid
connection, the inverter is not allowed to connect to the grid.
According to the standards of certain countries and regions, after the
inverter is powered on for the first time for grid connection, if the power
grid voltage is lower than Startup frequency lower threshold of grid
connection, the inverter is not allowed to connect to the grid.
The standards of certain countries and regions require that after the inverter
shuts down for protection due to a fault, if the power grid voltage is higher
than Grid reconnection voltage upper limit, the inverter is not allowed to
reconnect to the grid.
The standards of certain countries and regions require that after the inverter
shuts down for protection due to a fault, if the power grid voltage is lower
than Grid reconnection voltage lower limit, the inverter is not allowed to
reconnect to the grid.
The standards of certain countries and regions require that after the inverter
shuts down for protection due to a fault, if the power grid frequency is
higher than Grid reconnection frequency upper limit, the inverter is not
allowed to reconnect to the grid.
The standards of certain countries and regions require that after the inverter
shuts down for protection due to a fault, if the power grid frequency is
lower than Grid reconnection frequency lower limit, the inverter is not
allowed to reconnect to the grid.
Specifies the voltage threshold for triggering reactive power compensation
based on the cosφ-P curve.
Specifies the voltage threshold for exiting reactive power compensation
based on the cosφ-P curve.
Copyright © Huawei Technologies Co., Ltd.