Graco Fluid Automation 633 Operation page 32

Meter-mix dispense systems
Table of Contents

Advertisement

Screen Identification
These screens indicate that the machine was not able to refill its plungers properly. The likely cause for this is the
feed system was not able to provide material. It is detected by monitoring the pressure in each cylinder during a refill.
If installed, refer to the SR657-1M-LR Meter-Mix Dispense Systems-Operation manual for additional details.
This event may be configured as an Alert or a Warning on the Alarm Setting Screen. A warning will allow the machine
to keep dispensing; an alert will stop and prevent dispensing until the tank is filled.
The pressure in the metering unit cylinder is below the expected value. Verify the following:
Be out of material.
Have an open valve.
Have a bad plunger seal.
Have a bad cylinder check valve.
32