Menu 2: "Block & Reset Alarms - Eaton CEAG LP-STAR Mounting And Operating Instructions

Compact emergency power supply
Table of Contents

Advertisement

7 Operating
7 .4 .2 Menu 2: "Block & Reset Alarms"
Overview:
Block device
Release device
Main menu
Manual reset
Reset DeepDischarge
Test & Statusmenu
Block & Reset Alarms
Basic setup
Circuit setup
Luminaire setup
Logbooksetup
Send ServicePinMsg
Menu 2
Block device
Release device
Manual reset
Reset DeepDischarge
Reset ISO-failure
Selection of the
Block device
menu points
Release device
with the
Manual reset
keys
Reset DeepDischarge
<ok>:
confirm
selection
<Menu>: Exit
and return to
Block device
previous menu
Release device
Manual reset
(with input of
Reset DeepDischarge
any changes
made)
<ESC>: Exit
and return to
previous menu
(without input
of any changes
made)
flashing input
Block device
prompt
Release device
Manual reset
Reset DeepDischarge
Release device
Manual reset
Reset DeepDischarge
Reset ISO-failure
36
Mounting and operating instructions compact emergency power supply CEAG LP-STAR 40071860247 (L) September 2018 www.ceag.de
Blocked (Menu)
<ok>
U= 20,5V
Menu 2.1:
Error message
L1:
L2:
Use key
to select from the
options shown.
<ok>
Normal operation
Menu 2.2:
U= 20,5V
Error message
L1:
L2:
(Menu 2.3: only direct to the station)
<ok> triggers the function, if this option
has been activated under menu point 3
"Basic setup":
If the option "Manual Reset (On)" has been
activated (Menu "Basic setup/ Manual
Reset") there is no automatic resumption
of normal operations following power
(Menu 2.4: only direct to the station)
<ok> triggers the function:
After the error message "Deep Discharge
Protection" in the default display, receipt
of the message is acknowledged with this
menu point.
(Menu 2.5: only direct to the station)
<ok>
<ok> triggers the function:
I= 0,2A
All functions are aborted;
All exits are switched voltage free!
L3:
There is no battery operation in the event
of mains power failure.
During maintenance work at final circuits
they must also be disconnected. (see 8.3
Enabling of end circuits with maintenance
work)
<ok> triggers the function:
The selected stations are unblocked and
I= 0,2A
resume operations.
L3:
recovery after a power failure.
This ensures that the emergency lighting
remains on until it has been confirmed
that, for example, in a cinema, the normal
lighting has been reactivated.
The controls return to normal operations if
there are no further error messages.
After the error message "Deep Discharge
Protection" in the default display the
batteries must be checked and changed
if necessary.
Upon confirmation the controls for the LP-
STAR station return to normal operations if
there are no further error messages.