Huawei SUN2000-63KTL-JPH0 User Manual page 101

Hide thumbs Also See for SUN2000-63KTL-JPH0:
Table of Contents

Advertisement

SUN2000-63KTL-JPH0
User Manual
Alarm
Alarm Name
ID
2063
Cabinet
Overtemperature
2064
Device Fault
2065
Upgrade Failed
2066
License Expired
61440
Faulty Monitoring
Unit
Issue 06 (2020-02-18)
Alarm
Cause
Severity
long time and the power
cable is not well insulated
to ground.
Minor
Cause ID = 1
1. The SUN2000 is installed
in a place with poor
ventilation.
2. The ambient temperature
exceeds the upper
threshold.
3. The SUN2000 is not
working properly.
Major
Cause ID = 1–15
An unrecoverable fault occurs
on a circuit inside the
SUN2000.
Minor
Cause ID = 1–4
The upgrade ends abnormally.
Warning
Cause ID = 1
1. The privilege certificate
has entered the grace
period.
2. The privilege feature will
be invalid soon.
Minor
Cause ID = 1
1. The flash memory is
Copyright © Huawei Technologies Co., Ltd.
8 Maintenance
Measures
for the SUN2000 is
correctly connected.
3. If you are sure that the
impedance is less than
the default value in a
cloudy or rainy
environment, reset
Insulation resistance
protection.
1. Check the ventilation
and ambient temperature
at the SUN2000
installation position. If
the ventilation is poor or
the ambient temperature
exceeds the upper
threshold, improve the
ventilation and heat
dissipation.
2. If the ventilation and
ambient temperature
both meet requirements,
contact Huawei technical
support.
Turn off the AC output
switch and DC input switch,
and then turn them on after
15 minutes. If the fault
persists, contact Huawei
technical support.
NOTE
Cause ID = 1: Perform the
preceding operations when the
PV string current is less than 1
A.
1. Perform an upgrade
again.
2. If the upgrade fails
several times, contact
your dealer.
1. Apply for a new
certificate.
2. Load the new certificate.
Turn off the AC output
switch and DC input switch,
and then turn them on after
94

Advertisement

Table of Contents
loading

Table of Contents