Procedure
Proceed as follows:
1. Configure the ET 200S (with the IM 151/CPU) as an S7-300 station.
– Create a new station of the type S7-300 (Insert
command).
– Change to the hardware configuration window for this station.
– In the "Hardware Catalog" window, select the PROFIBUS-DP/ET 200S/IM
151/CPU folder.
– Drag and drop the "IM 151/CPU" object in the empty station window.
– Configure the ET 200S with the required I/O modules.
– Save the station (i.e. the ET 200S).
2. Configure a DP master (e.g. CPU with integrated PROFIBUS-DP interface or
CP 342-5 with PROFIBUS-DP interface as of 6GK7 342-5DA01-0XE0,
version 2) in another station in the same project.
3. Drag the ET 200S (with the IM 151/CPU) from the "Hardware Catalog" window
(from the configured stations) container and drop it on the icon for the DP
master system.
4. Double-click the intelligent DP slave icon, and select the "Interconnecting" tab.
Specify on this tab which station is to represent the intelligent DP slave.
5. Select the intelligent DP slave, and click the "Interconnect" button.
6. Select the (slave) configuration tab, and assign the master and slave
addresses.
7. Click "OK" to accept the settings.
8. The two stations must then be reloaded to start master-slave communication.
Configuration in a Non-Siemens System
Using the DDB file you can also integrate the IM 151/CPU in non-Siemens
systems as a DP standard slave. In this case the diagnostic frame consists of the
following:
Station Status
Master PROFIBUS Address
Manufacturer ID
Module Diagnostics
Module Status
ET 200S Interface Module IM 151/CPU
A5E00058783-01
Commissioning and Diagnostics
Station) menu
4-3