Instruction List
B.15
Timer Instructions
Starting or resetting of a timer (addressed directly or via a parameter). The
duration must be in ACCU1-L.
In-
stru-
Address
Address
ction
ID
SP
T
Start timer as pulse on edge change from
"0" to "1"
"0" t "1"
Timer
para.
SE
T
Start timer as extended pulse on edge
change from "0" to "1"
h
Timer
para.
SD
T
Start timer as ON delay on edge change
f
from "0" to "1"
Timer
para.
SS
T
Start timer as retentive ON delay on edge
change from "0" to "1"
h
Timer
para.
SF
T
Start timer as OFF delay on edge change
f
from "1" to "0"
Timer
para.
FR
T
Enable timer for restarting on edge
change from "0" to "1" (reset edge me-
h
Timer
mory marker for starting timer)
para.
R
T
Reset timer
Timer
para.
Status word for:
SP, SE, SD, SS, SF, FR, R
Instruction depends on:
Instruction controls:
*
+ time for loading the address of the instruction
** With direct instruction addressing
B-28
Description
Description
f
"0" t "1"
"0" t "1"
f
"0" t "1"
"1" t "0"
f
"0" t "1" (
t d
BR
A1
Length
Typical Execution Time in
in
Words
Direct Ad-
dressing
1**/2
9.2
2
1**/2
9.2
2
1**/2
9.7
2
1**/2
9.7
2
1**/2
10.0
2
1**/2
2.1
2
1**/2
1.8
2
A0
OV
OS
OR
0
ET 200S Interface Module IM 151/CPU
s
Indirect Ad-
*
dressing
9.7+
9.7+
10.2+
10.2+
10.5+
2.7+
2.4+
STA
RLO
/FC
Yes
0
A5E00058783-01