Configuration Frame and Parameter Assignment Frame for the ET 200S
Configuration Frame with the Default Setting for Address Areas
If you don't parameterize the IM 151/CPU and therefore don't specify any address
areas for data transfer with the DP master, the IM 151/CPU will start up after
commissioning with a default setting on the PROFIBUS-DP.
In the figure below you will find the configuration frame for the default setting:
16 words of input data; unit consistency (i.e. word)
16 words of output data; unit consistency (i.e. word)
Table A-4
Structure of the Configuration Frame with Default Setting for the Address Areas (Normal
Identifier Format in Accordance with AKF)
Configured
Address
Areas
1.
2.
3.
4.
5.
ET 200S Interface Module IM 151/CPU
A5E00058783-01
Byte
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
7
6
5
4
3
2
1
0
0
1
0 1
1 1
1
1
Length of the input data: 16 words
Input data:
Length specified in words
Consistency over words
7
6
4
3
2
1
0
5
0
1
1
0
1 1
1
1
Length of the output data: 16 words
Output data
Length specified in words
Consistency over words
Bit no.
Bit no.
A-5