Relays
Relay outputs 1 to 4 are normally On Point/Off Point relays which may be used to start/stop pumps or open/close valves at
different levels. They normally energise at one level and de-energise at a different level.
Alternatively, they may be programmed as out-of-limits alarms such that they are energised between defined points and will de-
energise outside the defined limits. They may also be programmed to perform a variety of auto-sequences and auxiliary
functions, such as pump-down operations, pump rotations to equalise wear, and desludge/cleaning.
Relay output 5 is normally a fail safe fault relay but may be re-allocated to another duty.
Relays can be set-up easily using the Relay Wizard, accessible by navigating to the RELAYS menu screen.
Relay (RL) Status
The relay status icons on the primary display have the following meanings:
= energised
0
= de-energised
A
= Alarm
S
= Sampler
T
= Totalising
Comfort (System) Settings
The SETTINGS menu allows adjusting of the time and date, switching off the keyboard sound and changing language.
January 2006
Navigating to the RELAY Screen
Relay is presently energised.
Relay is presently de-energised.
All active alarms can be viewed by parameter D831.
Relay is allocated to sampling duty.
Relay is allocated to totalising duty.
Navigating to the SETTINGS Menu