Quick-start booklet
IP2040/QS
MSP-USTD1/MSP-USTD2
January 2006
Quick-start: For MSP-USTD1/MSP-USTD2
www.mobrey.com

Advertisement

loading

Summary of Contents for Emerson mobrey MSP-USTD1

  • Page 1 Quick-start booklet IP2040/QS MSP-USTD1/MSP-USTD2 January 2006 Quick-start: For MSP-USTD1/MSP-USTD2 www.mobrey.com...
  • Page 2 Introduction What is this Quick-start? This Quick-Start is for anyone who has to install and commission the MSP-USTD1 or MSP-USTD2 ultrasonic system, and does not need in-depth information. For full installation instructions, you must refer to the installation (IM) manuals supplied with the equipment. What are these MSP-USTD1 and MSP-USTD2 systems? They are level, contents, or flow measurement and control systems.
  • Page 3: Installation

    Installation IMPORTANT - For hazardous area installations, you must refer to the installation (IM) manuals supplied with the system. Location of MSP900SH • Install the transmitter above the liquid surface using the bracket provided. • Do not mount the MSP900SH on a structure that is subject to vibration, or in a position where damage may be caused by impact or thermal stress.
  • Page 4: Getting Started

    Getting started After completing the installation of both MCU901 control unit and the MSP900SH transmitter, the next stage is to switch on. Familiarise yourself with the front panel fascia. Key to figure: 4-line LCD with backlight. Keypad with 6 function keys. Status LED –...
  • Page 5 Press the yellow (ENTER) key to display the top-level of the menu system. The primary display re-appears automatically if there is no keypad activity for several minutes, if on-line. In addition, it re-appears when pressing the ESC key whilst at the top level of the menu system. How to display the menu system Navigation of the menu system is achieved by using the ARROW...
  • Page 6 Application/Duty: Level Measurement With power on and the MSP900SH transmitter giving a 4-20mA signal to the MCU901 unit (see previous pages), you can now programme the MCU901 for an application. This application example is for level measurement. Requirements Live level measurement in units of metres over a range of 0 to 11.7 metres. High level alarm.
  • Page 7 Application Example: Level Measurement using Duty Wizard January 2006 (IP2040/QS)
  • Page 8 Application/Duty: Wet Well (with Pump Control) With power on and the MSP900SH transmitter giving a 4-20mA signal to the MCU901 unit (see previous pages), you can now programme the MS901 for an application. This application example is for a Wet Well with pump control. Requirement •...
  • Page 9 Application Example: Wet Well using Duty Wizard January 2006 (IP2040/QS)
  • Page 10 Application/Duty: Contents Measurement With power on and the MSP900SH transmitter giving a 4-20mA signal to the MCU901 unit (see previous pages), you can now programme the MCU901 for an application. This application example is for contents measurement. Requirement Live contents measurement in units of litres. Low level alarm at 2000 litres.
  • Page 11 Application Example: Contents measurement using the Duty Wizard January 2006 (IP2040/QS)
  • Page 12 Application/Duty: Flow Measurement With power on and the MSP900SH transmitter giving a 4-20mA signal to the MCU901 unit (see previous pages), you can now programme the MCU901 for an application. This application example is for flow measurements. Requirement Live flow measurements in units of cubic metres per second. Totalised flow in cubic metres per second.
  • Page 13 Application Example: Flow Measurements using Duty Wizard January 2006 (IP2040/QS)
  • Page 14: Other Features

    Other Features Restoring factory defaults (Erases all user entered data) To re-set the MCU901 unit back to the factory defaults, navigate to the “Load Defaults” screen and press the ENTER key twice. Navigating to the LOAD DEFAULTS Screen PIN Security Personal Identification Number (PIN) security prevents unauthorised people from programming the MCU901 control unit.
  • Page 15 Relays Relay outputs 1 to 4 are normally On Point/Off Point relays which may be used to start/stop pumps or open/close valves at different levels. They normally energise at one level and de-energise at a different level. Alternatively, they may be programmed as out-of-limits alarms such that they are energised between defined points and will de- energise outside the defined limits.
  • Page 16 Mobrey, Mobrey Measurement, and the Mobrey logotype are registered trademarks of Mobrey Limited. The Emerson logo is a trade mark and service mark of Emerson Electric Co. “Brand mark listing” are marks of one of the Emerson Process Management family of companies.