Example 3: Optaf Board With External Safety Relay Module With Or Without Reset For Safe Torque Off (Sto) Or En 60204-1 Stop Category 0 - Vacon OPTAF User Manual

Vacon nx sto and atex option board
Table of Contents

Advertisement

vacon • 26
3.4.3
Example 3: OPTAF board with external safety relay module with or
without reset for Safe Torque Off (STO) or EN 60204-1 stop category 0
MAIN CIRCUIT
PE
L1
L2
L3
PE
1
3
5
F1
SPEED REFERENCE
2
4
6
R1
W12
1sh
1r
PE
L1
L2
L3
1
+10Vref
X10
X2
2
7
U
V
W
PE
PE
PE
PE
W1
U1
V1
W1
M
PE
3
~
PE
1
2
M1
Figure 10 presents a connection example of OPTAF board for STO safety function with external
safety relay module and without reset.
External safety relay module is connected to the switch S1. The used power supply to switch S1 is
230 VAC as an example. The safety relay module is connected to OPTAF board with 4 wires as shown
in Figure 10.
When the switch S1 is activated (contacts open), the drive will go to STO state and motor (if running)
will stop by coasting. The drive will indicate: "A30 SafeTorqueOff".
When switch S1 is released (contacts closed), the drive returns to the ready state. The motor can
then be run with a valid start command.
The external relay can be wired so that manual reset is required to reset the STO safety function.
More information regarding the safety relay module may be found from the safety relay documen-
tation.
NOTE! For EN 60204-1 emergency stop according to stop category 0, use emergency stop button.
* Switch S1 in the figure can be replaced with the gate switch, then only Safe torque off mode is required. In
normal operation, both contacts are closed.
CONTROL UNIT
CCW
S
CW
2sh
2p
2s
PE
1
2
3
4
5
6
7
2
3
4
5
6
7
AIA1+
AIA1
AIA2+
AIA2
+24V
GND
SD1+
SD1
SD2+
SD2
RO1 NC
RO1 C
1
2
3
4
21
EXAMPLE:
DOLD BN5930.48/204230VAC
PE
PE
PE
W3
1r
2r
SafeDisable
A1
T11
T12
A10
K3.1
K1.2
13
23
14
24
K1
A2
S23
For automatic reset
link X2 and T22
(Not allowed with Emergency stop)
0V
+24V
Shortcircuit and
earth fault protected supply
Figure 10. Example 3.
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
START
STOP
S6
S7
13
11
14
12
8
9
10
11
12
13
8
9
10
11
12
13
DIN1
DIN2
DIN3
CMA
+24V
GND
A B
C D
A B C D
A B
C D
B
X1
X2
X3
X6
A
RO1 N O
RO2 C
RO2 NO
TI1+
TI1
OFF
X10
OPTAF
SLOT B
22
23
25
26
28
29
ON
T22
X2
K 1. 1
K3.2
K2.2
28
K 2. 1
29
K2
K3
STO AND SS1 SAFETY FUNCTIONS
Alternative : Gate Switch *
31
32
11
S2
Open
12
13
S3
14
33
34
14
15
16
17
18
19
14
15
16
17
18
19
20
DIN4
D IN5
DIN 6
CMB
AOA1+
AOA1
DOA1
OPTA1
Basic I/O
SLOT A
S1
12
11
2
L1
26
230Vac
22
21
1
N
27
W1
20
PE
9
Vacon
START
res et
+
STO P
s elect
enter
Shortcircuit and
earth fault
protected supply
11059.emf