Accessories - Riello GAS 9/2 Installation, Use And Maintenance Instructions

Forced draught gas burners
Table of Contents

Advertisement

L=130
L1 = 314 mm
(A)
Code 3000876
L = 444 mm
Code 3010028
L1 = 574 mm
(B)
Code 3000781
mm
A
B
D1
350
1210
(C)
(D)
C1
C2
D1
H
C
MIN
1170
1150
D91
D90
kg
MAX
1820
198
D39
D40
4

ACCESSORIES

(optional)
SPACER FOR SHORTENING THE COMBUS-
TION HEAD (A) Code 3000723
L = Spacer thickness
L1= Resulting blast tube length
KIT FOR LPG OPERATION (B)
This kit must be fitted whenever the burner is to
be operated on LPG.
L = kit for standard length head
L1 = kit for head lengthened with (A)
SOUNDPROOFING (C)
The sound damping casing significantly reduces
the noise generated by the burner (-14/18 dBA).
The casing is in steel and sound-damping mate-
rial and fully encloses the burner.
The casing is wheel-mounted so that it can be
easily removed for burner inspection.
KIT FOR CONTINUOUS VENTILATION
Code 3010030
The kit comprises a small three-way solenoid to
be installed between the air pressure switch
6)(A)p.5 and the fan.
It allows the burner to fire again after it has re-
mained under continuous ventilation following
flame cut-out.
KIT FOR TOWN GAS OPERATION
Code 3010298
This kit must be fitted whenever the the burner is
to be operated on town gas.
Code is suitable for the both standard and ex-
tended head.
FLAME SENSOR KIT Code 3010359
SUPPORT (D) Code 3000731
The support should be fitted to burner with a long
head (574). It is designed to bear the Wight of the
burner during head inspection. For burner with a
short head, the support is not essential although
useful.
The 1" 1/2 pipe of the support should be pre-
pared by the installer to a length appropriate to
that of the system.
The base is fitted with a wheels.
RADIO DISTURBANCE PROTECTION KIT
Code 3010386
If the burner is installed in places particularly
subject to radio disturbance (emission of signals
exceeding 10 V/m) owing to the presence of an
INVERTER, or in applications where the length
of the thermostat connections exceeds 20
metres, a protection kit is available as an inter-
face between the control box and the burner.

Advertisement

Table of Contents
loading

This manual is also suitable for:

1114 t2001405720014058

Table of Contents