Model PAD-5
1
Wiring and Configuring the PAD-5-MB
X300
Pin
1
2
3
4
Admissible cable cross-section: 1 x 12...18 AWG or 2 x 16...18 AWG
X400
Pin
1
2
3
4
Admissible cable cross-section: 1 x 12...18 AWG or 2 x 16...18 AWG
24
Siemens Industry, Inc.
Smart Infrastructure
Designation
Description
NAC1_+
Positive feed for notification appliances for NAC 1 Class A or CLASS
B
NAC1_-
Return feed for notification appliances for
NAC 1 Class A or CLASS B;
NAC2_+
Positive feed for notification appliances for NAC Class A or NAC 2
Class B
NAC2_-
Return feed for notification appliances for NAC 1 Class A or NAC 2
Class B
Designation
Description
NAC3_+
Positive feed for notification appliances for NAC 2 Class A or NAC 3
CLASS B
NAC3_-
Return feed for notification appliances for
NAC 2 Class A or NAC 3 CLASS B;
NAC4_+
Positive feed for notification appliances for NAC 2 Class A or NAC 4
Class B
NAC4_-
Return feed for notification appliances for NAC 2 Class A or NAC 4
Class B