3.2.2.2
3.2.2.3
Siemens Industry, Inc.
Smart Infrastructure
NACs (1-4) Configured as Auxiliary Circuits
When NAC 1 and NAC2 are configured for auxiliary output through the configuration
tool, the outputs are always on, unless the software is programmed for special pur-
poses. Refer to the configuration tool Zeus manual for specifics when configuring
the NACs for auxiliary output. These circuits are Power Limited.
X300
Pin
Designation
1
NAC1_+
2
NAC1_-
3
NAC2_+
4
NAC2_-
Admissible cable cross-section: 1 x 12-18 AWG or 2 x 16-18 AWG
X400
Pin
Designation
1
NAC3_+
2
NAC3_-
3
NAC4_+
4
NAC4_-
Admissible cable cross-section: 1 x 12-18 AWG or 2 x 16-18 AWG
NACs (1-4) Configured as Shorting Device Inputs
NAC 1 through NAC 4 can be configured through configuration tool ZEUS as Short-
ing Device Inputs, i.e. for monitoring dry relay contacts. Wiring and configuration is
limited to Class B and these inputs can be configured as Supervisory, Status or
Trouble inputs. The input devices must be of shorting type.
X300
Pin
Designation
1
NAC1_+
2
NAC1_-
3
NAC2_+
4
NAC2_-
Admissible cable cross-section: 1 x 12-18 AWG or 2 x 16-18 AWG
Wiring and Configuring the PAD-5-MB
Description
Positive feed for Auxiliary Circuit 1 (DC +24 V)
Return feed for Auxiliary Circuit 1 (DC -24 V)
Positive feed for Auxiliary Circuit 2 (DC +24 V)
Return feed for Auxiliary Circuit 2 (DC -24 V)
Description
Positive feed for Auxiliary Circuit 3 (DC +24 V)
Return feed for Auxiliary Circuit 3 (DC -24 V)
Positive feed for Auxiliary Circuit 4 (DC +24 V)
Return feed for Auxiliary Circuit 4 (DC -24 V)
Description
Positive feed for Contact Input Circuit 1
Return feed for Contact Input Circuit 1
Positive feed for Contact Input Circuit 2
Return feed for Contact Input Circuit 2
Model PAD-5
1
25