Danfoss VLT MCB 113 Operating Manual page 37

Hide thumbs Also See for VLT MCB 113:
Table of Contents

Advertisement

Operating Guide | VLT® Extended Relay Card MCB 113
Option
[195]
RS Flipflop 3
[196]
RS Flipflop 4
[197]
RS Flipflop 5
[198]
RS Flipflop 6
[199]
RS Flipflop 7
[221]
IGBT cooling
[222]
Homing OK
[223]
On target
[224]
Position limit
[225]
Position error
[226]
Touch on target
[231]
In power lim. mot.
[232]
In power lim. gen.
[233]
In power limit
Danfoss A/S © 2020.01
Function
See parameter group 13-1* Comparators.
See parameter group 13-1* Comparators.
See parameter group 13-1* Comparators.
See parameter group 13-1* Comparators.
See parameter group 13-1* Comparators.
Use this option for handling the overcurrent trips. When the drive detects an overcurrent condition,
it shows alarm 13, Overcurrent and triggers a reset. If the overcurrent condition occurs for the 3
time in a row, the drive shows alarm 13, Overcurrent and initiates a 3-minute delay before the next
reset.
This option is available only with software version 48.xx for VLT® AutomationDrive FC 302.
Homing is completed with the homing function selected in parameter 17-80 Homing Function.
This option is available only with software version 48.xx for VLT® AutomationDrive FC 302.
Positioning is completed and the on-target signal is sent when the actual position is within parame-
ter 3-05 On Reference Window for the duration of parameter 3-09 On Target Time and the actual speed
does not exceed parameter 3-05 On Reference Window.
This option is available only with software version 48.xx for VLT® AutomationDrive FC 302.
The position error exceeds the value in parameter 4-71 Maximum Position Error for the time set in
parameter 4-72 Position Error Timeout.
This option is available only with software version 48.xx for VLT® AutomationDrive FC 302.
The position is outside the limits set in parameter 3-06 Minimum Position and parameter 3-07 Maxi-
mum Position.
This option is available only with software version 48.xx for VLT® AutomationDrive FC 302.
Touch probe positioning active. The drive monitors the touch probe sensor input.
N O T I C E
N O T I C E
N O T I C E
N O T I C E
N O T I C E
AQ322553864968en-000101 / 130R0353| 37