Modbus Registers - Siemens OpenAir GMA 1 Series Technical Basics

Actuators with spring return
Hide thumbs Also See for OpenAir GMA 1 Series:
Table of Contents

Advertisement

32/44
Siemens
Building Technologies

7.3.4 Modbus registers

Reg.
Name
Process Values
1
Setpoint
2
Override control
3
Actual position
256
Command
Parameters
257
Opening direction
258
Adaptive Mode
259
Operating Mode
260
MinPosition
261
MaxPosition
262
Actuator Running Time
513
Backup Mode
514
Backup Position
515
Backup Timeout
516
Startup Setpoint
764
Modbus Address
765
Baudrate
766
Transmission Format
767
Bus Termination
768
Bus Conf. Command
769
Status
GMA..1 actuators with spring return
R/W
Unit
Scaling
RW
%
0.01
RW
--
--
R
%
0.01
RW
--
RW
--
--
RW
--
--
RW
--
--
RW
%
0.01
RW
%
0.01
R
s
1
RW
--
--
RW
%
0.01
RW
s
1
RW
%
0.01
RW
--
--
RW
--
--
RW
--
--
RW
--
--
RW
--
--
--
--
R
Range / enumeration
0..100
0 = Off / 1 = Open / 2 = Close
3 = Stop / 4 = GoToMin / 5 = GoToMax
0..100
0 = Ready / 1 = Adaption / 2 = Selftest
3 = ReInitDevice / 4 = RemoteFactory
Reset
0 = CW / 1 = CCW
0 = Off / 1 = On
1 = POS
0..100
0..100
90
0 = Go to BackupPosition
1 = Keep last position
2 = Disabled
0..100
0..65535
0..100
1..247 / 255 = "unassigned"
0 = auto / 1 = 9600 / 2 = 19200
3 = 38400 / 4 = 57600 / 5 = 76800
6 = 115200
0 = 1-8-E-1 / 1 = 1-8-O-1
2 = 1-8-N-1 / 3 = 1-8-N-2
0 = Off / 1 = On
0 = Ready / 1 = Load / 2 = Discard
See below, Register 769 "Status"
CM2Z4614en
2018-01-11