7.3.4 Modbus registers

Reg.
Name
Process Values
1
Setpoint
2
Override control
3
Actual position
256
Command
Parameters
257
Opening direction
258
Adaptive Mode
259
Operating Mode
260
MinPosition
261
MaxPosition
262
Actuator Running Time
513
Backup Mode
514
Backup Position
515
Backup Timeout
516
Startup Setpoint
764
Modbus Address
765
Baudrate
766
Transmission Format
767
Bus Termination
768
Bus Conf. Command
769
Status
Rotary actuators without spring return GBB/GIB..1
Commissioning notes
R/W
Unit
Scaling
RW
%
0.01
RW
--
--
R
%
0.01
RW
--
RW
--
--
RW
--
--
RW
--
--
RW
%
0.01
RW
%
0.01
R
s
1
RW
--
--
RW
%
0.01
RW
s
1
RW
%
0.01
RW
--
--
RW
--
--
RW
--
--
RW
--
--
RW
--
--
--
--
R
Range / enumeration
0..100
0 = Off / 1 = Open / 2 = Close
3 = Stop / 4 = GoToMin / 5 =
GoToMax
0..100
0 = Ready / 1 = Adaption / 2 =
Selftest
3 = ReInitDevice / 4 =
RemoteFactory Reset
0 = CW / 1 = CCW
0 = Off / 1 = On
1 = POS
0..100
0..100
150
0 = Go to BackupPosition
1 = Keep last position
2 = Disabled
0..100
0..65535
0..100
1..247 / 255 = "unassigned"
0 = auto / 1 = 9600 / 2 = 19200
3 = 38400 / 4 = 57600 / 5 = 76800
6 = 115200
0 = 1-8-E-1 / 1 = 1-8-O-1
2 = 1-8-N-1 / 3 = 1-8-N-2
0 = Off / 1 = On
0 = Ready / 1 = Load / 2 =
Discard
See below, Register 769 "Status"
CE1Z4626en
2019-11-28

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents