Modbus Registers - Siemens OpenAir GEB 1 Series Technical Basics

Actuators without spring return
Hide thumbs

Advertisement

Siemens
Building Technologies

7.3.4 Modbus registers

Reg.
Name
Process Values
1
Setpoint
2
Override control
3
Actual position
256
Command
Parameters
257
Opening direction
258
Adaptive Mode
259
Operating Mode
260
MinPosition
261
MaxPosition
262
Actuator Running Time
513
Backup Mode
514
Backup Position
515
Backup Timeout
516
Startup Setpoint
764
Modbus Address
765
Baudrate
766
Transmission Format
767
Bus Termination
768
Bus Conf. Command
769
Status
Technische Grundlagen: Drehantriebe GEB...1
R/W
Unit
Scaling
RW
%
0.01
RW
--
--
R
%
0.01
RW
--
RW
--
--
RW
--
--
RW
--
--
RW
%
0.01
RW
%
0.01
R
s
1
RW
--
--
RW
%
0.01
RW
s
1
RW
%
0.01
RW
--
--
RW
--
--
RW
--
--
RW
--
--
RW
--
--
--
--
R
Range / enumeration
0..100
0 = Off / 1 = Open / 2 = Close
3 = Stop / 4 = GoToMin / 5 =
GoToMax
0..100
0 = Ready / 1 = Adaption / 2 =
Selftest
3 = ReInitDevice / 4 =
RemoteFactory Reset
0 = CW / 1 = CCW
0 = Off / 1 = On
1 = POS
0..100
0..100
150
0 = Go to BackupPosition
1 = Keep last position
2 = Disabled
0..100
0..65535
0..100
1..247 / 255 = "unassigned"
0 = auto / 1 = 9600 / 2 =
19200
3 = 38400 / 4 = 57600 / 5 =
76800
6 = 115200
0 = 1-8-E-1 / 1 = 1-8-O-1
2 = 1-8-N-1 / 3 = 1-8-N-2
0 = Off / 1 = On
0 = Ready / 1 = Load / 2 =
Discard
See below, Register 769
"Status"
31/44
CM2Z4621en
2017-05-26