Siemens OpenAir GMA 1 Series Technical Basics page 36

Actuators with spring return
Hide thumbs Also See for OpenAir GMA 1 Series:
Table of Contents

Advertisement

Outputs
Position indicator
for GMA16..1
Feedback potentiometer
for GMA132.1
Auxiliary switch
for GMA..6.1, GMA164.1,
Connection cables
Degree of protection of housing
Protection class
Environmental conditions
Standards and directives
Dimensions
Weight
36/44
Siemens
Building Technologies
Output signal (wires 9-2)
Output voltage U
Max. output current
Protected against faulty wiring
Change of resistance (wires P1-P2)
Load
Max. sliding contact current
Permissible voltage at potentiometer (SELV/PELV)
Insulation resistance between potentiometer and housing
AC power supply
Switching voltage
Nominal current res./ind.
Life: 6 A res., 2 A ind.
without load
DC power supply
Switching voltage
Nominal current
Electric strength auxiliary switch against housing
Switching range for auxiliary switches
Setting increments
Switching hysteresis
Factory switch setting
Switch A
Switch B
Cross section of prewired connection cables
Standard cable length
Permissible length for signal lines (non-communicative types)
Degree of protection as per EN 60 529
Insulation class
AC/DC 24 V, Feedback potentiometer
AC 230 V, Auxiliary switch
Operation
Climatic conditions
Mounting location
Temperature
Humidity (non-condensing)
Transport
Climatic conditions
Temperature
Humidity (non-condensing)
Mechanical conditions
Product safety
Automatic electrical controls for household and similar use
Electromagnetic compatibility
(Application)
EU Conformity (CE)
RCM Conformity
EAC Conformity
UL, cUL
Product environmental declaration
Actuator W x H x D (see "Dimensions")
Damper shaft
Round
Square
Min. length
Max. shaft hardness
Weight without packaging
GMA1..1
GMA321.1, 326.1
GMA161.1E/MO
1)
The documents can be downloaded from
2)
The product environmental declaration contains data on environmentally compatible product design
and assessments (RoHS compliance, materials composition, packaging, environmental benefit,
disposal).
GMA..1 actuators with spring return
DC 0...10 V
DC ° 1 mA
max. AC 24 V/DC 24 V
0...1000 ς
< 1 W
< 10 mA
max. AC 24 V/DC 24 V
AC 500 V
AC 24...230 V
6 A / 2 A
10
10
DC 12..30 V
DC 2 A
AC 4 kV
5°...90°
85°
0.75 mm
0.9 m
300 m (see chapter 6)
IP 54
as per EN 60 730
lll
II
IEC 60 721-3-3
class 3K5
interior, weather-protected
,32....+55 °C
< 95 % r.h.
IEC 60 721-3-2
class 2K3
,32...+70 °C
< 95 % r.h.
class 2M3
EN 60 730-2-14, (Type 1)
For residential, commercial and industrial
environments
8000081792
8000081793
Eurasia conformity for all GMA.. variants
UL 873 http://ul.com/database
2)
CE1E4614en
81 x 192 x 63 mm
6.4...20.5 mm
6.4...13 mm
20 mm
< 400 HV
1.2 kg
1.3 kg
1.4 kg
http://siemens.com/bt/download
4
cycles
6
cycles
2
1)
1)
1)
and A6V101083254en