Festo CPV GE-ASI-8E8A-Z M8 Series Brief Description page 21

Valve terminal with as-interface

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 17
If by mistake, the same address is assigned to both slaves,
clear access to the slaves is no longer possible. In this case
proceed as follows:
1. Use the address selector button to uncouple slave 1
from the AS−Interface bus.
2. Modify the address of slave 2.
3. Lock the address selector button again, in order to
couple slave 1 to the AS−Interface bus again.
3.3 Assigning the AS−Interface addresses with
addressing devices < Spec. 2.1
Caution
Slave 1 must never have address #31. Otherwise
further modification of the addresses is no longer
possible.
For faultless operation the addresses must be
assigned consecutively (e.g. slave 1: #5; slave 2: #4
or slave 1: #4; slave 2: #5).
Recommendation: Select the addresses so that a
complete byte in the PLC address range is assigned
to the valve terminal.
Festo CPV..−GE−ASI−8E8A−Z M8 0306c English
21