Festo CPV GE-ASI-8E8A-Z M8 Series Brief Description page 19

Valve terminal with as-interface

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 17
3
Installation instructions
3.1 AS−Interface addresses
Before connecting to the AS−Interface bus: assign an un
used address to each slave.
Please note
Valve terminal type CPV..−GE−ASI−8E8A−Z M8 contains
2 AS−Interface slaves coupled together. The CPV−...
behaves on the AS−Interface bus like two individual
valve terminals each with 4 inputs and 4 outputs
(valve locations).
Assignment of the inputs and outputs (valves):
Automatic addressing with the function Automatic
address assignment" of the master is not possible.
It is not necessary to parametrize the AS−Interface
slaves.
Address assignment
The assignment of the data bits to the inputs and outputs
of both independent slaves is shown in the following dia
gram.
Data bits:
Inputs:
Outputs:
I/O = Bidirectional (B)
The address mapping depends on the configuration of the
master.
Festo CPV..−GE−ASI−8E8A−Z M8 0306c English
slave 1: Inputs I0 ... I3; Outputs O0 ... O3
slave 2: Inputs I4 ... I7; Outputs O4 ... O7.
Slave 1: IO code 7
D0
D1
I/O
I/O
I0
I1
O0
O1
Slave 2: IO code 7
H
D2
D3
D0
I/O
I/O
I/O
I2
I3
I4
O2
O3
O4
H
D1
D2
D3
I/O
I/O
I/O
I5
I6
I7
O5
O6
O7
19