Electric Installation; Circuit Diagrams - PFAFF silberblau Beta Silverline Operating Instructions Manual

Electric wire rope winch
Table of Contents

Advertisement

Available languages

Available languages

Electric wire rope winch >BETA< SILVERLINE
English

Electric Installation

Works on the electric installation may only be effected:
with cleared power supply
by trained and qualified electricians
Observe the regulations and standards of electric
engineering.
In Germany, VDE regulations do apply.
For controlling the winch, an electric control is
required.
The respective standard electric control fitted to the electric
wire rope winch is delivered with the winch.
Observe the instructions mentioned below as well as the
technical regulations of the respective country if the electric
control is provided on site. , i.e. EN 60204 T1 and T32,
The manufacturer of the electric control takes the
responsibility.
Indication EMV
The el. winch with control is designed for industry.
The winch has to be switched at max. 5 times/mi-
nute
to
accomplish the standards for elec-
tromagnetic emissions EN DIN 50081-2). EMV pro-
ceedings (e.g. line filter) have to be carried out if the
winch has to be switched more than 5 times/minute
or by using other electronic switching circuits (on
site or delivered as option).
Electric controls can be delivered as:
direct control
max. motor power 2,2 kW
1) circuit diagram no. 4.1.401 - 0750
2) circuit diagram no. 4.1.431 - 0750
Contactor control
electric control with mounted-in reversing con-
tactor, thermal motor protection, main switch and
integrated operating elements
1) circuit diagram no. 4.1.401 - 0700(3)
2) circuit diagram no. 4.1.431 - 0700(3)
electric control with mounted-in reversing con-
tactor, thermal motor protection, main switch,
main contactor and external operating elements
1) circuit diagram no. 4.1.401 - 0710(3)
2) circuit diagram no. 4.1.431 - 0710(3)
electric control with mounted-in reversing con-
tactor, thermal motor protection, main switch ,
main contactor and electronic overload pro-
tection *
1) circuit diagram no. 4.1.401 - 0720(3)
2) circuit diagram no. 4.1.431 - 0720(3)
* Wire rope winches with a load of 1000 kg and more have to
be equipped with an overload protection.
1) electric wire rope winch >BETA< SILVERLINE with 1 wire
rope speed and AC connection
2) electric wire rope winch >BETA< SILVERLINE with 1 wire
rope speed and single-phase AC
Pfaff-silberblau
contactor control
Winches with AC connection
f=50 Hz: 380÷420 V
Type of protection IP 54
Operating voltage 42 V - 50/60 Hz
technische Änderungen vorbehalten
up to
980kg
up to
1000 kg
Option
from
1000 kg
are designed for:
f=60 Hz: 440÷460 V
design changes under reserve
04.01.401
Attention
When connecting the
winch to a three-phase
network U=440÷460V,
the bridge of the trans-
former has to be switched
from A÷B to B÷C !
Winches with single-phase AC
f=50 Hz: 220÷240V single-phase AC
Type of protection IP 54
Operating voltage 24 V - 50 Hz
For supply of the control current circuit, a transformer
with galvanic separation must be used (provided in
Pfaff-silberblau controls) Exception direct control acc.
to EN 60204 T32 § 9.1, § 9.2.5.10.
In any case, an easily accessible emergency stop push-
button (switch) has to be provided. (provided in Pfaff-
silberblau controls, different designs)
Emergency-stop switch
An emergency shut-off switch must be located at
each control point and must be quickly and easily
accessible. Where necessary, there must also be an
additional device for emergency stop, like f. e
around an unprotected winch.
Main switch
For design with direct control a main switch must
be provided on site.
In contactor control a main switch is included.
Main current fuses / Feed cable /

Circuit diagrams

Main current fuses must be provided on site.
Nominal current consumption with three-phase, 400V,
50Hz or 440V, 60Hz and rec. excess current devices
(fuses).
driving power
short circuit pro-
[kW]
0,25; 0,3; 0,31; 0,37
0,94; 1,38
Nominal
current
consumption
420/240V, and rec. excess current devices (fuses).
driving power
short circuit pro-
I
tection (inert) [A]
N
[kW]
0,37
2,5
Attention!
When using longer cables one must consider an additional
loss of current. Consult your electrical engineer.
The connecting cables are to be laid in suitable cable chan-
nels or protection tubes.
Sharp edges, wire edges, rough surfaces or screw threads
which the cable wires may come in to contact with, must be
removed from around the cable channels.
If a control is provided on site, the circuit diagram of
the manufacturer has to be presented. Observe the
valid regulations.
The connection of the wire rope winch always has to
be effected according to the circuit diagram included
into delivery or to that provided on site!
changements techniques sous réserve
Transformator
transformer
380-420V 440-460V
380-420V 440-460V
rec. feed cable
tection (inert)
cross-section
[A]
NYM - J [mm²] Cu
4
4 x 1,5
6
4 x 1,5
with
single-phase
rec. feed cable
cross-section
NYM - J [mm²] Cu
10
4 x 1,5
Seite / page 19

Advertisement

Table of Contents
loading

Table of Contents