Compressor Capacity Steps; Correction Tables - Lochinvar Amicus LAHP302WW Installation, Commissioning, User And Maintenance Instructions

Boost
Table of Contents

Advertisement

C
OMPRESSOR CAPACITY STEPS
Model
302
402
602
702
902
1202
1402
1804
2304
2604
C
ORRECTION TABLES
Operation with glycol
Glycol percentage
Freezing point (°C)
10
20
30
40
50
CCF: Capacity correction factor
WFCF: Water flow correction factor
The water flow rate and pressure drop correction factors are to be applied directly to the values given for operation
without glycol. The water flow rate correction factor is calculated in order to maintain the same temperature
difference as that which would be obtained without glycol. The pressure drop correction factor takes into account
the different flow rate obtained from the application of the flow rate correction factor.
Correction data tables at different Δt
Water temperature diff.(°C)
CCCP = Cooling capacity correction factor IPCF = Input power correction factor
Correction tables different Fouling factors
CCCP = Cooling capacity correction factor IPCF = Input power correction factor
Page | 17
50%
50%
50%
50%
50%
50%
50%
25%
25%
25%
CCF
-3.2
0.985
-7.8
0.98
-14.1
0.97
-22.3
0.965
-33.8
0.955
IPCF: Input power correction factor
PDCF: Pressure drops correction factor
CCCP
IPCF
Fouling factor
CCCP
IPCF
No Of Compressors
1
IPCF
1
0.99
0.98
0.97
0.965
3
0.99
0.99
0.00005
1
1
2
3
50%
--
50%
--
50%
--
50%
--
50%
--
50%
--
50%
--
25%
25%
25%
25%
25%
25%
WFCF
9
1.02
1.05
16
1.09
1.14
1.2
1
5
1
1
0.00001
0.98
0.98
4
--
--
--
--
--
--
--
25%
25%
25%
PDCF
1.08
1.12
1.22
1.25
1.33
8
1.01
1.02
0.00002
0.94
0.95