Amicus
Boost Heat Pumps
Installation, commissioning, user
and maintenance instructions
READ AND UNDERSTAND THE
INSTRUCTIONS
Read and fully understand all instructions
before attempting to operate maintain or
install the unit.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Amicus LAHP302WW and is the answer not in the manual?

Questions and answers

Summary of Contents for Lochinvar Amicus LAHP302WW

  • Page 1 Amicus Boost Heat Pumps Installation, commissioning, user and maintenance instructions Models: LAHP302WW LAHP1202WW READ AND UNDERSTAND THE LAHP402WW LAHP1402WW INSTRUCTIONS LAHP602WW LAHP1804WW LAHP702WW LAHP2304WW Read and fully understand all instructions LAHP902WW LAHP2604WW before attempting to operate maintain or install the unit. Installation manual_Boost heat pump_July2019 Page | 1...
  • Page 2: Table Of Contents

    TABLE OF CONTENTS 1. INTRODUCTION ..................................... 5 Preliminary information ..............................5 Aim and content of the manual ............................5 How to store this manual .............................. 5 Manual Update ................................5 How to use this manual ..............................5 Potential Risks ................................. 6 General Description of Symbols Used ..........................
  • Page 3 Installation of rubber vibration dampers (KAVG) ....................... 22 Serial interface card RS485 (INSE) ............................ 23 Source water pump installation ............................24 Hydraulic connections ..............................24 Chemical characteristics of the water ..........................25 User circuit minimum water content ..........................25 Installation with source open circuit (water to water heat pump) ..................26 Chemical characteristics of source water circuit.........................
  • Page 4 Display alarm history ..............................48 7. MAINTENANCE OF THE UNIT ................................. 49 General warnings ................................49 Drive access .................................. 49 Periodical checks ................................49 Every 6 months ................................49 End of seasons or unit switched off ..........................50 Refrigerant circuit repair ..............................50 8.
  • Page 5: Introduction

    The Lochinvar Limited will not be liable for claims for damage caused to persons, animals, material goods or property caused by improper installation, adjustment and maintenance or improper use. Any use not specified in this manual is prohibited.
  • Page 6: Potential Risks

    OTENTIAL ISKS Whilst the unit has been designed to minimize any risk posed to the safety of people who will interact with it, it has not been technically possible to eliminate completely the causes of risk. It is therefore necessary to refer to the requirements and symbolism below: LOCATION OF RISK POTENTIAL RISK...
  • Page 7: General Description Of Symbols Used

    ENERAL ESCRIPTION OF YMBOLS Safety symbols combined in accordance with ISO 3864-2: BANNED A black symbol inside a red circle with a red diagonal indicates an action that should not be performed. WARNING A black graphic symbol added to a yellow triangle with black edges indicates danger.
  • Page 8: Safety Symbols Used

    AFETY SYMBOLS USED GENERAL RISK Observe all signs placed next to the pictogram. The failure to follow directions may create a risk situation that may be injurious to the user. ELECTRICAL HAZARD Observe all signs placed next to the pictogram. The symbol indicates components of the unit and actions described in this manual that could create an electrical hazard.
  • Page 9: Unit Identification

    NIT IDENTIFICATION Each unit has a rating plate that provides key information regarding the machine. The rating plate may differ from the one shown below as the example is for a standard unit without accessories. For all electrical information not provided on the label, refer to the wiring diagram. A facsimile of the label is shown below: The product label should never be removed from the unit.
  • Page 10: Safety

    SAFETY ARNING RE POTENTIALLY HAZARDOUS TOXIC SUBSTANCES Identification of the Type of Refrigerant Fluid Used: R134a  Tetrafluoroethane (HFC134a) 100% by weight CAS No.: 000811-97-2 Identification of the Type of Oil Used.  The lubricant used is polyester oil. Please refer to the information provided on the compressor data plate. For further information regarding the characteristics of the refrigerant and oil used, refer to the safety data sheets available from the refrigerant and oil manufacturers.
  • Page 11: Prevent Inhalation Of High Vapour Concentration

    REVENT INHALATION OF HIGH VAPOUR CONCENTRATION Atmospheric concentrations of refrigerant must be minimized and kept to a level that is below the occupational exposure limit. Vapour is heavier than air and can form dangerous concentrations near the ground where the ventilation rate is lower. Always ensure adequate ventilation.
  • Page 12: Technical Characteristics

    TECHNICAL CHARACTERISTICS NIT DESCRIPTION Amicus boost heat pumps are particularly suitable for applications that use source energy at medium or high temperatures. These units have been designed to produce water at high or very high temperature for applications where it is necessary to have maximum efficiency in heating.
  • Page 13: Accessories Description

    CCESSORIES DESCRIPTION Rubber vibration dampers (KAVG) To be installed beneath the unit base and the ground to avoid the transmission of vibrations (and the noise) to the building. Pressure gauges (MAML) These enable the standing charge and the operating pressures to be monitored. Electronic soft starter (DSSE) It is used to reduce the peak current of the unit;...
  • Page 14: Technical Data

    ECHNICAL DATA Model LAHPXXXXWW 1202 1402 1804 2304 2604 Heating capacity (EN14511) 37,6 43,6 64,1 75,1 97,8 121,7 150,5 195,6 243,9 301,2 Input power (EN14511) 11,1 13,7 17,6 21,7 26,2 35,0 43,1 52,2 COP (EN14511) 5,65 5,83 5,79 5,48 5,56 5,62 5,74 5,59...
  • Page 15: Operation Limits

    (D.H.W.). The units must be used for this specific purpose only. Lochinvar Limited will not be liable for claims for damage caused to persons, animals or material goods or property caused by improper installation, adjustment and maintenance or improper use. Any use not specified in this manual is prohibited.
  • Page 16: Domestic Hot Water Production

    Special, enhanced surface area coils for use with smaller heat pumps (<20kW) and plate heat exchanger/buffer tank combinations for larger units should be used. Both options are available from Lochinvar Limited. Page | 16...
  • Page 17: Compressor Capacity Steps

    OMPRESSOR CAPACITY STEPS No Of Compressors Model 1202 1402 1804 2304 2604 ORRECTION TABLES Operation with glycol Glycol percentage Freezing point (°C) IPCF WFCF PDCF -3.2 0.985 1.02 1.08 -7.8 0.98 0.99 1.05 1.12 -14.1 0.97 0.98 1.09 1.22 -22.3 0.965 0.97 1.14...
  • Page 18: Sound Data

    OUND DATA Amicus Boost Heat pump Octave bands (Hz) Mod. dB(A) dB(A) 78.1 69.3 63.2 61.7 60.6 55.2 51.8 42.7 78.9 78.1 69.3 63.2 61.7 60.6 55.2 51.8 42.7 78.9 83.1 74.3 68.2 66.7 65.6 60.2 56.8 47.7 83.9 86.1 77.3 71.2 69.7...
  • Page 19: Installation

    INSTALLATION ENERAL SAFETY GUIDELINES AND USE OF SYMBOLS Before undertaking any task the operator must be fully trained in the operation of the machines to be used and their controls. They must also have read and be fully conversant with all operating instructions. All maintenance must be performed by TRAINED personnel and be in accordance with all national and local regulations.
  • Page 20: Inspection

    In Case of Damage • List the damage on the delivery note • Inform the Lochinvar Limited of the extent of the damage within 8 days of receipt of the goods. After this time any claim will not be considered.
  • Page 21: Lifting And Handling

    IFTING AND HANDLING When unloading the unit, it is highly recommended to avoid any sudden move in order to protect refrigerant circuit, copper tubes or any other unit component. Units can be lifted by using a forklift or, in alternative, using belts, being sure that the method of lifting does not damage the lateral panels and the cover.
  • Page 22: Clearances

    LEARANCES Mod. 1000 1000 1000 1000 1000 1202 1000 1402 1000 Mod. 1804 1000 1000 2304 1000 1000 2604 1000 1000 (KAVG) NSTALLATION OF RUBBER VIBRATION DAMPERS All units should be installed on vibration dampers in order to prevent the transmission of vibration to the supporting surface and reduce the noise level.
  • Page 23: Serial Interface Card Rs485 (Inse)

    Mod. 302÷602 88 mm 52 mm 41 mm 25 mm 11 mm 67 mm 10 mm 65 mm 74,5 mm 5,5 mm 702÷1402 88 mm 52 mm 41 mm 25 mm 11 mm 67 mm 10 mm 65 mm 74,5 mm 5,5 mm 1804÷2604 88 mm 52 mm...
  • Page 24: Source Water Pump Installation

    (inverter type) is used. The Lochinvar Limited states that it is of fundamental importance the correct flow rate of water source in order to avoid problems of freezing of the source heat exchanger. In this regard it is noted that the source water pump should be exclusively dedicated to the heat pump and, must be working as an on/off type control.
  • Page 25: Chemical Characteristics Of The Water

    System return water must be fitted to the connection labelled: ”USER WATER IN” as incorrect connection can damage the heat exchanger by freezing. It is compulsory to install on the USER WATER IN connection, a water strainer with a mesh not larger than 1 mm. Fitting this filter is COMPULSORY and the warranty will be invalidated if it is removed.
  • Page 26: Installation With Source Open Circuit (Water To Water Heat Pump)

    The limit values in the table may cause clogging by mud in the pipes and the heat exchanger. The maintenance of the quality of ground water is borne by the user and / or maintenance Lochinvar Limited. The temperature of source groundwater at the inlet of the source heat exchanger in heating mode, must not fall below 7.8 ° C to avoid freezing problems in the source circuit.
  • Page 27: Hydraulic Components

    YDRAULIC COMPONENTS Flow Switch User heat exchanger Source heat exchanger Page | 27...
  • Page 28: Typical Installation

    YPICAL INSTALLATION The pump must be installed with the water supply facing the water inlet connection Page | 28...
  • Page 29: Domestic Hot Water (Dhw) Hydraulic Circuit

    The above value does not guarantee the availability of an adequate domestic hot water flow to the user and its correct temperature over the long term; this value must be calculated according to the DHW load of the site. Please contact Lochinvar for help sizing the DHW load.
  • Page 30 Electric connections: preliminary safety information The electric panel is located inside the unit at the top of the technical compartment where the various components of the refrigerant circuit are also to be found. To access the electrical board, remove the front panel of the unit: Power connections must be made in accordance to the wiring diagram enclosed with the unit and in accordance to the norms in force.
  • Page 31: Electric Data

    The line voltage fluctuations cannot be more than ±10% of the nominal value, while the voltage unbalance between one phase and another cannot exceed 1%, according to EN60204. If those tolerances should not be respected, please contact our Lochinvar Limited. Model...
  • Page 32: Electric Connections

    LECTRIC CONNECTIONS Remote wiring connections (compulsory) The numbering of the terminals may change without notice. For their connection is mandatory to refer to the wiring diagram supplied along with the unit. All terminals referred to in the explanations below are present on the terminal board inside the electrical box, all electric connections mentioned below and have to be made by the installer, on site.
  • Page 33: Remote Wiring Connections (Optional)

    Remote wiring connections (optional) 33 | P a g e...
  • Page 34: Factory Fitted Wiring Connections

    Factory fitted wiring connections 34 | P a g e...
  • Page 35: Positioning Of The User Circuit Water Inlet Sensor (Bti)

    (BTI) OSITIONING OF THE USER CIRCUIT WATER INLET SENSOR The correct positioning of the BTI sensor is extremely important to guarantee the correct operation of the heat pump. The BTI sensor is used to cycle the unit to maintain the user water temperature at set point. The BTI sensor is also used to activate the user water pump and to stop it when the user water temperature set point is reached.
  • Page 36: Positioning Of The Domestic Hot Water Circuit Sensor (Bts)

    (BTS) OSITIONING OF THE DOMESTIC HOT WATER CIRCUIT SENSOR Correct positioning of the BTS sensor Incorrect positioning of the BTS sensor 36 | P a g e...
  • Page 37: Refrigerant Circuit Layout

    EFRIGERANT CIRCUIT LAYOUT Source water input probe High pressure pressostat Source water output probe Low-high pressure switch High pressure transducer Source side Low pressure transducer Shut off valve BTFI Free-cooling probe (inlet water plant) Sanitary side User water input probe User side V3SW5 User water output probe...
  • Page 38: Unit Start Up

    UNIT START UP RELIMINARY CHECKS Before starting the unit the checks detailed in this manual of the electric supply and connections (par. 4.20), the hydraulic system (par. 4.11) and the refrigerant circuit (par. 5.1.4), should be performed. Start-up operations must be performed in accordance with the instructions detailed in the previous paragraphs. If it is required to switch the unit on and off, never do this using the main isolator: this should only be used to disconnect the unit from the power supply when the unit is to be permanently off.
  • Page 39: Safety Device Setting

    If the unit is required for heating/cooling only (without domestic hot water production) the internal parameter of the microprocessor FS1 has to be modified from 2 to 1 in order to avoid configuration alarms. Please contact Lochinvar Limited for support. Controls during unit operation •...
  • Page 40: Description Of The Control Panel

    ESCRIPTION OF THE CONTROL PANEL Display The instrument display is divided into three zones: Top left zone: the display shows the inlet water temperature, Bottom left zone: the display shows the inlet domestic hot water temperature (the digit SAN. Will appear), Right zone: icons.
  • Page 41 If pressed down for 5 seconds, it makes it possible to switch the unit on or off in chiller mode (and domestic hot water, if required). Each time this function is activated, the green led positioned just above the button will be switched ON. If pressed down for 5 seconds, it makes it possible to switch the unit on or off in heating mode (and domestic hot water, if required).
  • Page 42: Remote Control Panel

    EMOTE CONTROL PANEL Installation The remote control panel is mounted on a panel with 72x56 mm cut-out, fixed with screw. To obtain IP65 protection for the panel, use the rubber gasket RGW-V (optional). For wall mounting use the V-KIT plastic adapter as illustrated in the picture.
  • Page 43: Display Icons

    Display icons Icon Meaning Icon Meaning Celsius degrees General Alarm Electric heaters activated Compressor 1 User water pump Compressor 2 Water flow alarm Key function M makes it possible to enter the functions menu SET makes it possible to display or modify the set points. Selects a parameter or confirms a value in programming mode.
  • Page 44: Use

    WITCH THE UNIT ON In order to power the unit, turn the main switch in ON position. The display shows the User inlet water temperature and the Domestic hot water inlet water temperature. Legend Led blinking: Defrost cycle timeout activated; Led ON: Unit in cooling mode.
  • Page 45: Heating Mode

    Heating mode To start the unit in heating mode, press the key. The green led is on. If requested, the compressor safety delay countdown starts and the compressor icon flashes. The water pump will be activated after few seconds and then, once the compressor countdown has finished, the compressor starts and the icon remains on.
  • Page 46: How To Change The Set Points

    OW TO CHANGE THE SET POINTS When modifying or varying the machine’s operating parameters, make sure that you do not create situations that conflict with the other set parameters. The complete display of the 3 set points (heating, domestic hot water, cooling) is ONLY available when the unit is in stand- by mode.
  • Page 47: Adjustable Parameters

    Set point compensation 0÷15°C 10°C Password (Contact the Lochinvar Limited) The units are supplied with a very sophisticated control system with many other parameters that are not adjustable by the end user; these parameters are protected by a manufacturer password.
  • Page 48: Acoustic Signal Silencing

    RST label appears on the upper part of the display. In this case press the key to reset. Non reset alarms: nO label appears on the upper part of the display. In this case the alarm is permanent; contact the Lochinvar Limited service. Display alarm history Press the , key, then the...
  • Page 49: Maintenance Of The Unit

    Access to the unit once installed, should only be possible to authorized operators and technicians. The owner of the equipment is the Lochinvar Limited legal representative, entity or person owns the property where the machine is installed. They are fully responsible for all safety rules given in this manual and regulations. If it is not possible to prevent access to the machine by outsiders, a fenced area around the machine at least 1.5 meters away from external surfaces in which operators and...
  • Page 50: End Of Seasons Or Unit Switched Off

    End of seasons or unit switched off If the unit is to be left out of commission for a long period, the hydraulic circuit should be drained down. This operation is compulsory if the ambient temperature is expected to drop below the freezing point of the fluid in the circuit (water or Glycol mix).
  • Page 51: Disposal, Recovery And Recycling

    ISPOSAL RECOVERY AND RECYCLING The frame and components, if unusable, should be taken apart and sorted by type, especially copper and aluminium that are present in large quantities in the machine. All materials must be recovered or disposed in accordance with national regulations. RAEE Directive (EU Only) •...
  • Page 52: Diagnosis And Troubleshooting

    Configuration alarm ACF2 Configuration alarm ACF3 Configuration alarm ACF4 Configuration alarm Wrong configuration of microprocessor ACF5 Configuration alarm Contact the Lochinvar Limited. control system. ACF6 Configuration alarm ACF7 Configuration alarm ACF8 Configuration alarm ACF9 Configuration alarm Switch OFF the unit and, after few...
  • Page 53 Overload source fan alarm limits. source fan and, in case replace it. Compressor 1 input current outside C1tr Compressor 1 overload Contact the Lochinvar Limited operation limits. Compressor 2 input current outside C2tr Compressor 2 overload Contact the Lochinvar Limited operation limits.
  • Page 54: Dimensions

    DIMENSIONS See individual drawings for further details Dimensional Drawing Amicus LAHP WW Units 302-402-702-902-1202-1402...