YASKAWA VIPA System 300S Manual page 44

Hide thumbs Also See for VIPA System 300S:
Table of Contents

Advertisement

Chapter 3 Deployment
Start-up
behavior IM
353DP slave
3-22
After power on, the DP slave executes a self test. It controls its internal
functions and the communication via the backplane bus. After the error free
start-up, the bus coupler switches into the state "ready". In this state, the
DP slave gets its parameters from the DP master and, at valid parameters,
switches into the state "DataExchange" DE (DE is permanently on).
At communication errors at the backplane bus, the PROFIBUS slave
switches into STOP and boots again after app. 2 seconds. As soon as the
test has been completed positive, the RD-LED blinks.
Power On
ER-LED on
PW-LED on
Initialization
DP slave sets outputs
to "0" and takes over
the defined Profibus
address
ER-LED off
RD-LED blinks
DP slave receives
project data from DP
master
Project data conform
with real build-up?
yes
RD-LED on
DE-LED on
Release in-/outputs
Data exchange
Para-
no
meterization
error?
no
no
Configuration
error?
HB140E - IM - RE_353-1DP01 - Rev. 14/47
Manual VIPA System 300S
y
ER-LED and
RD-LED blinking
simultaneously
ER-LED and
y
RD-LED blinking
simultaneously

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vipa im 353-1dp01

Table of Contents