YASKAWA VIPA System 300S Manual page 37

Hide thumbs Also See for VIPA System 300S:
Table of Contents

Advertisement

Manual VIPA System 300S
Device
configuration
Data of the
function modules
HB140E - IM - RE_353-1DP01 - Rev. 14/47
Via the index A4h, the module configuration of DP slave can be monitored.
The assignment identification to module type can be found at the following
table:
Module type
DI 8
DI 8 - Alarm
DI 16
DI 14 / 2C
DI 32
DO 8
DO 16
DO 32
DIO 8
DIO 16
AI2
AI4
AI4 - fast
AI8
AO2
AO4
AO8
AI2 / AO2
AI4 / AO2
To access the function modules with the Siemens SIMATIC Manager the
module address, which can be set by properties, is used as ID.
Using the following record set no. as Index you get access for reading (R)
res. writing (W) to the listed function module elements:
Index
Access Description
R
Diagnostic – record set 0
00h
W
Write Module parameters
01h
R
Diagnostic – record set 1
Identification
Input byte
9FC1h
1FC1h
9FC2h
08C0h
9FC3h
AFC8h
AFD0h
AFD8h
BFC9h
BFD2h
15C3h
15C4h
11C4h
15C5h
25D8h
25E0h
25E8h
45DBh
45DCh
Chapter 3 Deployment
Output byte
1
-
1
-
2
-
6
6
4
-
-
1
-
2
-
4
1
1
2
2
4
-
8
-
8
-
16
-
-
4
-
8
-
16
4
4
8
4
3-15