Manual VIPA System 300S
Parameter data
IM 353-1DP01
DP-V1
HB140E - IM - RE_353-1DP01 - Rev. 14/47
At usage of the IM 353-1DP01 (DP-V1) you have the following parameter
data:
Byte
Bit 7 ... Bit 0
0
Bit 2 ... 0: 0 (fix)
Bit 3: 0 = WD-Timebase 10ms
1 = WD-Timebase 1ms
Bit 4: 0 (fix)
Bit 5: 0 = Publisher-Mode not available
1 = Publisher-Mode available
Bit 6: 0 = Fail-Safe-Mode not available
1 = Fail-Safe-Mode available
Bit 7: 0 = DP-V1 mode disable
1 = DP-V1 mode enable
1
Bit 0: Startup when expected/actual config. differ
(must always be 0 else a parameterization error
occures)
Bit 3 ... 1: 0 (fix)
Bit 4: 0 = V1: Vendor-specific interrupt not available
1 = V1: Vendor-specific interrupt available
Bit 5: 0 = V1: Diagnostic interrupt not available
1 = V1: Diagnostic interrupt available
Bit 6: 0 = V1: Hardware interrupt not available
1 = V1: Hardware interrupt available
Bit 7: 0 (fix)
2
08h (fix)
3
0Ah (fix)
4
81h (fix)
5
00h (fix)
6
00h (fix)
7
Bit 0: 0 = Identifier-related diagnostic enable
1 = Identifier-related diagnostic disable
Bit 1: 0 = Module status enable
1 = Module status disable
Bit 2: 0 = Channel-related diagnostic enable
1 = Channel-related diagnostic disable
Bit 7 ... 3: 0 (fix)
8
Bit 7 ... 0: 0 (fix)
9 ... 12 00h (fix)
1)
Using the Siemens SIMATIC Manager this value is automatically set and can not be
changed.
Chapter 3 Deployment
Default
C0h
70h
08h
0Ah
81h
00h
00h
00h
00h
00h
3-13