Download Print this page

Siemens LOK16 Series Manual page 8

Burner controls
Hide thumbs Also See for LOK16 Series:

Advertisement

Type summary (cont'd)
LGK16...
For flame supervision with flame detector QRA53.../QRA55... or ionization probe
Preferred use:
Flash-steam
generators
Type
LGK16.122A27*
Article
BPZ:LGK16.122A27
no.
t1
10 s
TSA
2 s
TSA´
2 s
t3
4 s
t3´
4 s
t3n
---
t4
6 s
t4´
6 s
t5
4 s
t6
10 s
t7
2 s
t8
30 s
t9
2 s
t10
6 s
t11
Optional
t12
Optional
t13
10 s
t16
4 s
t20
32 s
8/28
Building Technologies Division
The type references given below apply to the LGK16 without plug-in base and without
flame detector. For ordering information for plug-in bases and other accessories, see
Accessories.
Flash-steam
Also suited for
generators
direct-fired air
heaters)
LGK16.133A27
LGK16.322A27*
BPZ:LGK16.133A27
BPZ:LGK16.322A27
9 s
35.5 s
3 s
2 s
3 s
2 s
3 s
4 s
---
4 s
---
---
6 s
10 s
---
10 s
3 s
10 s
14.5 s
12 s
3 s
2 s
29 s
65 s
3 s
2 s
6 s
8 s
14.5 s
12 s
3 s
4 s
60 s
---
LGK16.333A27*
LGK16.335A27*
BPZ:LGK16.333A27
BPZ:LGK16.335A27
31.5 s
37 s
3 s
2.5 s
3 s
5 s
6 s
5 s
6 s
2.5 s
---
---
11.5 s
12.5 s
11.5 s
15 s
11.5 s
12.5 s
17 s
15 s
3 s
2.5 s
69 s
74 s
3 s
5 s
11.5 s
10 s
17 s
15 s
6 s
5 s
26 s
22 s
LGK16.622A27*
LGK16.635A27*
BPZ:LGK16.622A27
BPZ:LGK16.635A27
65 s
66 s
2 s
2.5 s
2 s
5 s
4 s
5 s
4 s
2.5 s
---
---
10 s
12.5 s
10 s
15 s
10 s
12.5 s
12 s
15 s
2 s
2.5 s
95 s
103 s
2 s
5 s
8 s
10 s
12 s
15 s
4 s
5 s
---
---
CC1N7785en