I N S TA L L AT I O N , O P E R AT I O N S A N D M A I N T E N A N C E M A N U A L
Size 5 – 300:15CT (Standard and Ambient Comp.)
Motor Full-Load
Amps 3-Ph,
Heater Number
3 Heater
109-118
119-128
129-138
139-155
156-168
169-184
185-200
201-221
222-237
238-262
263-270
Electronic overload table for fusible controllers
Tripping current is 120% of Dial setting. Motors
with 1.15-1.25 service factor, set dial to motor
FLA Motors with 1.0 service factor, set dial to 0.9
motor FLA.
NEMA
FLA Range
Catalog
Size
in Amps
Number
1
0.8 to 1.59
CR324CXD
1
1.6 to 3.19
CR324CXE
1
3.2 to 6.49
CR324CXF
1
6.5 to 12.8
CR324CXG
1
13 to 27
CR324CXH
2
13 to 25.6
CR324DXG
2
26 to 49.9
CR324DXH
2
50 to 100
CR324DXJ
3
17 to 34.9
CR324FXK
3
35 to 64.9
CR324FXL
3
65 to 90
CR324FXM
4
17 to 34.9
CR324FXK
4
35 to 64.9
CR324FXL
4
65 to 135
CR324FXM
32 to 64.0
CR324GXN
65 to 129.9
CR324GXP
130 to 270
CR324GXQ
130 to 259.9
CR324HXS
260 to 540
CR324HXT
Additional motor overload protection required for
MM200 abd MM300 relay applications with FLA less
than 6A.
Maximum Fuse
CR123
Rating
C592A
600
C630A
600
C695A
600
C778A
600
C867A
600
C955A
600
C104B
600
C113B
600
C125B
600
C137B
600
C151B
600
Max. Fuse in Amps
Class R 30
Class J 60
60
100
100
200
200
400
400
600
600 Class L 1200
Heaters for NEMA size 6 and 7 fused controllers
For continuous-rated motors with a service factor
of 1.15 to 1.25, select the appropriate heaters for
the motor full-load current. For continuous-rated
motors with a service factor of 1.0, multiply the
motor full-load current by 0.9 and use this value
to select heaters.
Overload relay tripping current in 40° C ambient is
the minimum value of full-load current multiplied
by 1.25. Provide short-circuit protection in
accordance with the National Electrical Code
Opening of the circuit breaker or power
fuse may be an indication that a fault
current has been interrupted. To provide
continued protection against fire or shock
hazard, examine all current-carrying parts
and other components of the motor
controller and replace any damaged
components. If heater burnout occurs, the
complete overload relay must be replaced.
Overload heaters for controllers with NEMA
Size 6 starters for standard and ambient-
compensated ratings, CT ratio 600:5.
Maximum Motor
Current Transformer
Full-Load Current
Secondary Amps
181-197
1.51-1.64
198-214
1.65-1.78
215-238
1.79-1.98
239-258
1.99-2.15
259-290
2.16-2.42
291-346
2.43-2.88
347-387
2.89-3.22
388-423
3.23-3.53
424-467
3.54-3.89
468-516
3.90-4.30
517-540
4.31-4.50
Overload heaters for controllers with NEMA
Size 7 starters for standard and ambient-
compensated ratings, CT ratio 800:5.
Maximum Motor
Current Transformer
Full-Load Current
Secondary Amps
346-387
2.16-2.42
388-461
2.43-2.88
462-515
2.89-3.22
516-565
3.23-3.53
566-622
3.54-3.89
623-688
3.90-4.30
689-763
4.31-4.77
764-810
4.78-5.06
47
Heater Number
CR 123
C220A
C239A
C268A
C301A
C326A
C356A
C379A
C419A
C466A
C526A
C592A
Heater
Number
CR 123
C326A
C356A
C379A
C419A
C466A
C526A
C592A
C630A