Download Print this page

GE Evolution E9000 Series Installation, Operation And Maintenance Manual page 40

Motor control center
Hide thumbs Also See for Evolution E9000 Series:

Advertisement

E VO L U T I O N S E R I E S E 9 0 0 0 M OTO R C O N T R O L C E N T E R
40
Size 2 (Standard)
Motor
Full- Load
Amps 3-Ph,
3 Heater
8.81-9.27
9.28-9.99
10.0-11.1
11.2-12.1
11.2-12.1
12.2-13.0
12.2-13.0
13.1-15.5
15.6-16.8
16.9-18.0
18.1-19.7
19.8-21.6
21.7-23.9
21.7-23.9
24.0-25.5
24.0-25.5
25.6-26.0
25.6-28.2
28.3-31.6
31.7-34.7
34.8-37.8
37.9-40.6
40.7-43.4
Size 2 (Comp.)
Motor Full-
Load Amps
3-Ph, 3 Heater
9.04-9.61
9.62-10.5
10.6-11.6
11.7-12.5
11.7-12.5
12.6-13.0
12.6-13.6
13.7-16.7
16.8-17.9
18.0-18.7
18.8-20.4
20.5-22.7
22.8-24.7
22.8-24.7
24.8-26.0
24.8-26.3
26.4-29.5
29.6-32.5
32.6-36.7
36.8-41.9
42.0-43.2
43.3-43.4
Mag-Break Trip
Heater
TEC and
Number
TECL
CR123
Rating
Rec.
C104B
15
2
C113B
15
2
C125B
15
3
C137B
15
3
C137B
30
LO
C151B
15
4
C151B
30
LO
C163B
30
1
C180B
30
1
C198B
30
2
C214B
30
2
C228B
30
2
C250B
30
3
C250B
50
LO
C273B
30
3
C273B
50
LO
C303B
30
3
C303B
50
LO
C330B
50
1
C366B
50
2
C400B
50
2
C440B
50
3
C460B
50
3
Mag-Break
Heater
TEC and
Trip Setting
Number
TECL
CR123
Rating
Rec.
C104B
15
2
C113B
15
2
C125B
15
3
C137B
15
3
C137B
30
LO
C151B
15
4
C151B
30
LO
C163B
30
1
C180B
30
1
C198B
30
2
C214B
30
2
C228B
30
2
C250B
30
3
C250B
50
LO
C273B
30
4
C273B
50
LO
C303B
50
LO
C330B
50
1
C366B
50
2
C400B
50
2
C440B
50
3
C460B
50
3
Size 3 (Standard and Ambient Comp.)
Motor
Setting
Full-Load
Heater
Amps 3-Ph,
Number
Max.
3 Heater
CR123
5
17.8-18.4
F233B
6
18.5-21.1
F243B
6
21.2-22.1
F270B
7
22.2-26.0
F300B
2
26.1-28.0
F327B
8
28.1-31.3
F357B
2
31.4-33.3
F395B
3
33.4-34.3
F430B
4
34.4-40.9
F487B
5
41.0-43.4
F567B
5
43.5-44.7
F567B
6
44.8-51.0
F614B
7
51.1-52.0
F658B
2
52.1-55.4
F719B
8
55.5-63.3
F772B
3
63.4-66.1
F848B
9
66.2-73.5
F914B
3
73.6-82.2
F104C
4
82.3-86.9
F114C
5
Size 4 (Standard)
6
7
Motor
8
Full- Load
Heater
Amps 3-Ph,
Number
3 Heater
CR123
28.8-32.0
F357B
32.1-34.2
F395B
34.3-36.7
F430B
Max.
36.8-43.4
F487B
5
43.5-43.9
F487B
6
44.0-46.6
F567B
7
46.7-52.6
F614B
8
52.7-55.6
F658B
2
55.7-58.7
F719B
9
58.8-67.1
F772B
3
67.2-70.6
F848B
3
70.7-76.3
F914B
5
70.7-76.3
F914B
5
76.4-86.9
F104C
6
76.4-88.7
F104C
7
88.8-93.4
F114C
8
93.5-102
F118C
2
103-110
F133C
9
111-122
F149C
4
123-131
F161C
4
4
6
7
9
9
Mag-Break Trip
TEC and
Setting
TECL
Rating
Rec.
Max.
30
1
5
30
1
6
30
2
7
30
3
7
50
LO
4
50
LO
4
50
1
5
50
1
6
50
1
6
50
2
8
100
LO
3
100
LO
3
100
1
4
100
1
4
100
1
5
100
2
6
100
2
6
100
2
7
100
3
9
Mag-Break Trip
TEC and
Setting
TECL
Rating
Rec.
Max.
50
1
4
50
2
5
50
2
6
50
3
7
100
1
3
100
1
3
100
1
3
100
1
4
100
2
5
100
2
5
100
3
6
100
3
7
150
LO
1
100
4
8
150
LO
2
150
1
3
150
1
3
150
1
4
150
1
4
150
2
5

Hide quick links:

Advertisement

loading