Download Print this page

GE Evolution E9000 Series Installation, Operation And Maintenance Manual page 35

Motor control center
Hide thumbs Also See for Evolution E9000 Series:

Advertisement

I N S TA L L AT I O N , O P E R AT I O N S A N D M A I N T E N A N C E M A N U A L
Replacing a control power transformer
mounted under disconnect
Use the following procedure to replace a control
power transformer mounted under a disconnect.
1. Turn the power off.
2. Remove the saddle unit from the motor
control center.
3. Remove the top plate from the saddle unit.
4. Remove the handle assembly, as described
on page 15.
5. Remove line and load cables.
6. Loosen the screws securing the disconnect
assembly to the back plate and slide the
assembly out.
7. Disconnect the transformer power and
control leads.
8. Remove the transformer mounting screws
and lift out the transformer.
9. Install the new transformer by following this
procedure in the reverse order. Torque all
electrical connections.
Replacing a compact starter (1/2X)
Use the following procedure to replace
the starter.
1. Turn the power off.
2. Remove the saddle unit for the motor
control center.
3. Remove the pilot device bracket (it is not
required to remove control wiring)
4. Remove overload relay.
5. Use DIN rail release to gain access to line side
wiring of contactor, remove line wires.
6. Reverse to install new starter.
Suggested lifts
Example: Model No. 55B534913P1
• All welded construction;
• Positive lock winch system;
• 500 lb. capacity;
• Raised height 58";
• Lowered height 3-1/8Æ;
• 20" X 20" deck size;
• 10" load center;
• 2" X 6" molded-on-rubber casters.
The following instructions are available.
300 Line starter
GEH-5190 – NEMA Size 1 FVNR
GEH-4774 – NEMA Size 2 FVNR
GEH-4806 – NEMA Size 3 FVNR
GEH-4807 – NEMA Size 4 FVNR
GEH-4839 – NEMA Size 5 FVNR
GEH-5198 – NEMA Size 6 FVNR
GEH-5190 – NEMA Size 1 FVR and 2 Speed
GEH-4775 – NEMA Size 2 FVR and 2 Speed
GEH-4806 – NEMA Size 3 FVR and 2 Speed
GEH-4807 – NEMA Size 4 FVR and 2 Speed
GEH-4839 – NEMA Size 5 FVR and 2 Speed
GET-6915A - Tech Info.- Contact Appearance
Arc flash mitigation units
DEI-007 – Remote Racking System Instructions
DEI-009 – AFM Retrofit Assembly Instructions
DEI-010 – Manual Racking Handle Instructions
C-2000 contactors
GEH-6263 – CL02, CL025
GEH-6264 – CL045
GEH-6265 – CL08
GEH-6266 – CL10
GEH-6350 – CK08
GEH-6227 – CK095
GEH-6228 – CK10B, CK11B, CK12B
Solid state starters
DET-787 – ASTAT-BP
DEH-40397 – ASTAT-CD Plus
Relays
GEH-4115 – CR120B
GEH-6435 – ECM
AF600 Drives
DET-609 – AF-600FP Operating/Installation
DET-620 – AF-600FP Programming Guide
DET-623 – AF-600 FP/AF-650 GP
DET-624 – AF-600FP / AF-650 GP Profibus DP
DET-633 – AF-600 FP Analog I/O Instructions
DET-635 – AF-600 FP / AF-650 GP External
DC Supply
DET-607 – AF-650 GP Operating/Installation
DET-618 – AF-650 GP Programming Guide
Smart relays
MM300
GEK-113022 – Instruction Manual
GEK-113336 – Quick Start Guide
GEK-113392 – Communication Guide MM200
GEK-113400 – Instruction Manual
GEK-113401 – Quick Start Guide
GEK-113402 – Communication Guide
35

Hide quick links:

Advertisement

loading