Maytag Amana MEC96 Series Installation Instructions Manual page 8

Two-stage, fsp category iv direct or non direct vent air furnace
Table of Contents

Advertisement

Clearance in accordance with local installation codes, the
requirements of the gas supplier and the manufacturer's
installation instructions.
Dégaugement conforme aux codes d'installation locaux, aux
exigences du fournisseur de gaz et aux instructions
d'installation du fabricant.
Installations must adhere to the clearances to combustible
materials to which this furnace has been design certified. The
minimum clearance information for this furnace is provided
on the unit's clearance label. These clearances must be per-
manently maintained. Clearances must also accommodate
an installation's gas, electrical, and drain trap and drain line
connections. If the alternate combustion air intake or vent/
flue connections are used additional clearance must be provided
to accommodate these connections. Refer to Vent/Flue Pipe
and Combustion Air Pipe for details.
NOTE: In addition to the required clearances to combustible
materials, a minimum of 24 inches service clearance must
be available in front of the unit.
*MEC96 MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS
POSITION*
SIDES
REAR
Upflow
0"
0"
Horizontal
6"
0"
C = If placed on combustible floor, floor MUST be wood only.
*CEC96 MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS
POSITION*
SIDES
REAR
Counterflow
0"
0"
Horizontal
6"
0"
C = If placed on combustible floor, floor MUST be wood only.
NC = For installation on non-combustible floors only. A combustible subbase
must be used for installations on combustible flooring.
TOP
BOTTOM
A furnace installed in a confined space (i.e., a closet or utility
room) must have two ventilation openings with a total minimum
free area of 0.25 square inches per 1,000 BTU/hr of furnace
input rating. Refer to Specification Sheet applicable to your
model for minimum clearances to combustible surfaces. One
of the ventilation openings must be within 12 inches of the top;
(INCHES)
FRONT
BOTTOM
FLUE
3"
C
0"
3"
C
0"
(INCHES)
FRONT
BOTTOM
FLUE
3"
NC
0"
3"
C
0"
TOP
BOTTOM
Figure 1
the other opening must be within 12 inches of the bottom of
the confined space. In a typical construction, the clearance
between the door and door frame is usually adequate to satisfy
this ventilation requirement.
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being placed
into operation could result in carbon monoxide poisoning
or death.
The following steps shall be followed with each appliance
connected to the venting system placed in operation,
while any other appliances connected to the venting
system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and
horizontal pitch, as required by the National Fuel Gas
Code, ANSI Z223.1 or the Natural Gas and Propane
Installation Code, CSA B149.1-15 and these
instructions. Determine that there is no blockage or
restriction, leakage, corrosion and other deficiencies
which could cause an unsafe condition.
TOP
1"
3. As far as practical, close all building doors and
6"
windows and all doors between the space in which
the appliance(s) connected to the venting system are
located and other spaces of the building.
4. Close fireplace dampers.
TOP
5. Turn on clothes dryers and any appliance not
1"
connected to the venting system. Turn on any
6"
exhaust fans, such as range hoods and bathroom
exhausts, so they shall operate at maximum speed.
Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance
being inspected in operation. Adjust thermostat so
appliance shall operate continuously.
7. Test for spillage from draft hood appliances at the
draft hood relief opening after 5 minutes of main
burner operation. Use the flame of a match or
candle.
8. If improper venting is observed during any of the
above tests, the venting system must be corrected in
accordance with the National Fuel Gas Code ANSI
Z223.1/NFPA 54 and/or National Gas and Propane
Installation Code CSA B149.1-15.
9. After it has been determined that each appliance
connected to the venting system properly vents
when tested as outlined above, return doors,
windows, exhaust fans, fireplace dampers and any
other gas burning appliance to their previous
conditions of use.
8
WARNING

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents