Setting The Temperatures For The Heat Sink - Viessmann VITOTRONIC SPS Operating Instructions Manual

Heat pump control unit, type 2.0
Hide thumbs Also See for VITOTRONIC SPS:
Table of Contents

Advertisement

Setting the temperature
"Coolant buff. cyl."
Parameter
Set value int.
Start differential
Stop differential
"Cool.circ" (1/2/3/4)
Parameter
Set val.cooling
Cool. lim. day
Cool. lim. night

Setting the temperatures for the heat sink

The "Heat sink" includes the following system compo-
nents:
Heating water buffer cylinder "HWB"
DHW cylinder "HW"
"Booster htr"
Heating circuits "Circ. 1" to "Circ. 4"
Tap the following on-screen buttons:
1. If necessary,
for the home screen
2.
for the "Main menu"
"HWB" (heating water buffer cylinder)
Parameter
Set value int.
Set val. active cooling
Start differential
Stop differential
*1
The names can be changed.
(cont.)
Factory
Min.
Max.
setting
5 °C
3 °C
30 °C
3 K
0 K
10 K
0 K
0 K
10 K
Factory
Min.
Max.
setting
20 °C
5 °C
25 °C
24 °C
10 °C
30 °C
22 °C
10 °C
30 °C
*1
Factory
Min.
Max.
setting
40 °C
25 °C
60 °C
50 °C
25 °C
60 °C
3 K
0 K
10 K
0 K
0 K
10 K
Description
Fixed set buffer temperature for coolant buffer
cylinder ("Fix")
If the differential between the actual and set buf-
fer temperature is greater than this start differen-
tial, a demand is triggered.
If the differential between the actual and set buf-
fer temperature is smaller than this stop differen-
tial, the demand ends.
Description
Fixed set flow temperature for cooling circuit
("Fix")
Cooling limit during the day
Cooling limit at night
3. "Set val."
4. "Heat sink"
5. Select the system component, e.g. "Htg circ."
"Circ. 1".
6. "Set val."
7. Set the required values.
Description
Fixed set buffer temperature for heating water
buffer cylinder ("Fix")
Set value for parallel operation of coolant buffer
cylinder AC and heating water buffer cylinder
If the differential between the actual and set buf-
fer temperature is greater than this start differen-
tial, a demand is triggered.
If the differential between the actual and set buf-
fer temperature is smaller than this stop differen-
tial, the demand ends.
Settings
13