Device Features - Endress+Hauser Cerabar PMC11 Technical Information

Pressure transducer with ceramic and metal sensors
Hide thumbs Also See for Cerabar PMC11:
Table of Contents

Advertisement

Cerabar PMC11, PMC21, PMP11, PMP21

Device features

Endress+Hauser
1
PLC (programmable logic control)
2
e.g. RN221N / RMA42 (if required)
3
Pressure transducer
Field of application
• PMC11: Gauge pressure
• PMP11: Gauge pressure
• PMC21: Gauge and absolute pressure
• PMP21: Gauge and absolute pressure
Process connections
PMC11:
• Thread ISO 228
• Thread ASME
• DIN 13
PMP11:
• Thread ISO 228, also flush-mount
• Thread ASME
• DIN 13
PMC21:
• Thread ISO 228
• Thread DIN 13
• Thread ASME
• Thread JIS
PMP21:
• Thread ISO 228, also flush-mount
• Thread DIN 13
• Thread ASME
• Thread JIS
Measuring ranges
• PMC11: from –400 to +400 mbar (–6 to +6 psi) to –1 to +40 bar (–15 to +600 psi).
• PMP11: from –400 to +400 mbar (–6 to +6 psi) to –1 to +40 bar (–15 to +600 psi).
• PMC21: from –100 to +100 mbar (–1.5 to +1.5 psi) to –1 to +40 bar (–15 to +600 psi).
• PMP21: from –400 to +400 mbar (–6 to +6 psi) to –1 to +400 bar (–15 to +6 000 psi).
OPL (depends on the measuring range)
• PMC11: max. 0 to +60 bar (0 to +900 psi)
• PMP11: max. 0 to +160 bar (0 to +2 400 psi)
• PMC21: max. 0 to +60 bar (0 to +900 psi)
• PMP21: max. 0 to +600 bar (0 to +9 000 psi)
MWP
• PMC11: max. 0 to +60 bar (0 to +900 psi)
• PMP11: max. 0 to +160 bar (0 to +2 400 psi)
• PMP21: max. 0 to +600 bar (0 to +9 000 psi)
• PMC21: max. 0 to +60 bar (0 to +900 psi)
Process temperature range (temperature at process connection)
• PMC11: –25 to +85 °C (–13 to +185 °F)
• PMP11: –25 to +85 °C (–13 to +185 °F)
• PMC21: –25 to +100 °C (–13 to +212 °F)
• PMP21: –40 to +100 °C (–40 to +212 °F)
1
2
3
A0021926
9