Chapter 3 – Installation
Node ID selection
Programming
3-6
If the RDIO-01 module is mounted onto external I/O
Module Adapter AIMA-01, choose the proper node ID
for the module using the node ID selector (S1, range
1...15). Setting the node ID is not required when the
module is mounted into SLOT 1 or SLOT 2 on the drive.
The default setting of selector S1 is 2.
The communication between the module and the drive
is activated by a drive parameter. The RDIO-01 can
replace and/or extend certain standard inputs. See the
drive Firmware Manual, Parameter Group 98.
Note: The new settings take effect only when the
module is powered up.
RDIO-01 User's manual